{"title":"Effectiveness of the Seesaw System as a Means of Seismic Upgrading in Older, Non-Ductile Reinforced Concrete Buildings","authors":"Panagiota S. Katsimpini, G. Papagiannopoulos","doi":"10.3390/vibration6010008","DOIUrl":null,"url":null,"abstract":"This work investigates and discusses the effectiveness of the seesaw system when installed in an older, non-ductile reinforced concrete (RC) building for seismic upgrading purposes. In particular, two different configurations of the seesaw system are assumed in a two-storey 3D RC framed building which was designed according to older seismic provisions and, thus, is susceptible to flexural and shear failures. To check if there is any merit in employing the seesaw system in this RC building, non-linear time-history (NLTH) analyses are conducting using 11 seismic motions. Peak values for inter-story drift ratios (IDR), residual inter-story drift ratios (RIDR) and floor accelerations (FA) are computed, and the sequence and cause (i.e., due to surpass of flexural or shear strength) of plastic hinge formations are monitored. Leaving aside any issues related to fabrication and cost, interpretation of the results obtained by the aforementioned seismic response indices for the RC building under study leads to the conclusion that the seesaw system can be a retrofitting scheme for the seismic upgrading of older, non-ductile RC framed buildings.","PeriodicalId":75301,"journal":{"name":"Vibration","volume":" ","pages":""},"PeriodicalIF":1.9000,"publicationDate":"2023-01-21","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"4","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Vibration","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.3390/vibration6010008","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q3","JCRName":"ENGINEERING, MECHANICAL","Score":null,"Total":0}
引用次数: 4
Abstract
This work investigates and discusses the effectiveness of the seesaw system when installed in an older, non-ductile reinforced concrete (RC) building for seismic upgrading purposes. In particular, two different configurations of the seesaw system are assumed in a two-storey 3D RC framed building which was designed according to older seismic provisions and, thus, is susceptible to flexural and shear failures. To check if there is any merit in employing the seesaw system in this RC building, non-linear time-history (NLTH) analyses are conducting using 11 seismic motions. Peak values for inter-story drift ratios (IDR), residual inter-story drift ratios (RIDR) and floor accelerations (FA) are computed, and the sequence and cause (i.e., due to surpass of flexural or shear strength) of plastic hinge formations are monitored. Leaving aside any issues related to fabrication and cost, interpretation of the results obtained by the aforementioned seismic response indices for the RC building under study leads to the conclusion that the seesaw system can be a retrofitting scheme for the seismic upgrading of older, non-ductile RC framed buildings.