Seismic performance characterization of fire sprinkler piping systems through shake table testing

IF 0.8 Q4 ENGINEERING, GEOLOGICAL
Muhammad Rashid, R. Dhakal, T. Sullivan, T. Yeow
{"title":"Seismic performance characterization of fire sprinkler piping systems through shake table testing","authors":"Muhammad Rashid, R. Dhakal, T. Sullivan, T. Yeow","doi":"10.5459/bnzsee.55.3.167-182","DOIUrl":null,"url":null,"abstract":"Fire sprinkler systems damaged during earthquakes can compromise building functionality either by loss of fire protection and/or flooding damage. To characterize the seismic behavior of fire sprinkler piping systems, shake table tests were conducted on a piping specimen with features representative of actual practices in New Zealand. The specimen was subjected to a set of motions including recorded floor acceleration response histories of an instrumented building in New Zealand. This paper describes the test setup and the piping specimen, and discusses the seismic response of the specimen to multiple floor motions for different bracing variations. Based on the test results reported in this paper, it can be concluded that bracing segments of piping other than the distribution pipe, such as the branch and arm-over pipes, can considerably affect the seismic demand on the system. Further, the test results confirm that the seismic demands on pipes can be considerably greater if the piping system is in resonance with the input excitation motion.","PeriodicalId":46396,"journal":{"name":"Bulletin of the New Zealand Society for Earthquake Engineering","volume":" ","pages":""},"PeriodicalIF":0.8000,"publicationDate":"2022-09-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Bulletin of the New Zealand Society for Earthquake Engineering","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.5459/bnzsee.55.3.167-182","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q4","JCRName":"ENGINEERING, GEOLOGICAL","Score":null,"Total":0}
引用次数: 2

Abstract

Fire sprinkler systems damaged during earthquakes can compromise building functionality either by loss of fire protection and/or flooding damage. To characterize the seismic behavior of fire sprinkler piping systems, shake table tests were conducted on a piping specimen with features representative of actual practices in New Zealand. The specimen was subjected to a set of motions including recorded floor acceleration response histories of an instrumented building in New Zealand. This paper describes the test setup and the piping specimen, and discusses the seismic response of the specimen to multiple floor motions for different bracing variations. Based on the test results reported in this paper, it can be concluded that bracing segments of piping other than the distribution pipe, such as the branch and arm-over pipes, can considerably affect the seismic demand on the system. Further, the test results confirm that the seismic demands on pipes can be considerably greater if the piping system is in resonance with the input excitation motion.
通过振动台试验表征消防喷淋系统的抗震性能
消防喷淋系统在地震期间损坏,可能会因失去防火保护和/或洪水破坏而损害建筑物的功能。为了表征消防喷淋系统的抗震性能,在新西兰对具有代表性的管道试件进行了振动台试验。该试样受到一系列运动的影响,包括新西兰一座仪器化建筑的地板加速度响应历史记录。本文介绍了试验装置和管道试件,并讨论了不同支撑变化下管道试件在多次楼板运动下的地震反应。根据本文所报道的试验结果,可以得出结论,除配水管外,支管和移交管等管道的支撑段对系统的抗震需求有很大影响。此外,试验结果证实,当管道系统与输入激励运动发生共振时,对管道的抗震要求会大大提高。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
CiteScore
2.50
自引率
17.60%
发文量
14
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信