Natural ventilation performance for airborne diseases management in a deployable treatment facility.

IF 2.6 4区 医学 Q2 INFECTIOUS DISEASES
Infection Control and Hospital Epidemiology Pub Date : 2026-09-01 Epub Date: 2026-07-16 DOI:10.1017/ice.2026.10508
Luca Fontana, Gino Cortellessa, Giorgio Grossi, Anna Silenzi, Michele Di Marco, Antoine Chaillon, Robert Wunderlich, Giorgio Buonanno
{"title":"Natural ventilation performance for airborne diseases management in a deployable treatment facility.","authors":"Luca Fontana, Gino Cortellessa, Giorgio Grossi, Anna Silenzi, Michele Di Marco, Antoine Chaillon, Robert Wunderlich, Giorgio Buonanno","doi":"10.1017/ice.2026.10508","DOIUrl":null,"url":null,"abstract":"<p><strong>Objective: </strong>To assess whether wind-driven natural ventilation in the Infectious Diseases Treatment Module (IDTM) can achieve ventilation performance consistent with airborne precaution requirements [160 liters per second (L/s)] and to estimate associated pathogen-specific infection risks.</p><p><strong>Methods: </strong>An experimental campaign of air velocity measurements and CO<sub>2</sub> decays were conducted to validate the developed computational fluid dynamics (CFD) model. The validated CFD model simulated wind-driven natural ventilation (1-4 m/s) for an L-shaped IDTM configuration under four structural scenarios defined by the presence or absence of patient porches and mosquito nets. Airborne infection risk was estimated using a Wells-Riley quanta-based model for seven representative airborne pathogens under short-duration healthcare worker exposure and prolonged patient co-exposure.</p><p><strong>Results: </strong>Ventilation performance varied widely based on wind speed and structural configuration. Airflow ranged from 7 L/s in the most restricted configuration (porch and mosquito nets present at 1 m/s) to over 3,100 L/s when mosquito nets were removed at 4 m/s.When mapped to infection-risk estimates, ventilation rates at 160 L/s substantially reduced short-duration healthcare worker infection risk for all pathogens (≤1%), whereas prolonged co-exposure remained associated with high risk for high-emission pathogens despite high ventilation.</p><p><strong>Conclusion: </strong>Under favorable wind conditions and optimized configurations, the IDTM can achieve ventilation rates consistent with the 160 L/s recommendation for airborne precautions. While this provides substantial protection for healthcare workers, individual-room isolation remains essential for patient management. Operationally, removing window-mounted nets is the most effective way to ensure safety targets are met; hybrid ventilation measures should be considered during low-wind conditions.</p>","PeriodicalId":13663,"journal":{"name":"Infection Control and Hospital Epidemiology","volume":" ","pages":"894-900"},"PeriodicalIF":2.6000,"publicationDate":"2026-09-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Infection Control and Hospital Epidemiology","FirstCategoryId":"3","ListUrlMain":"https://doi.org/10.1017/ice.2026.10508","RegionNum":4,"RegionCategory":"医学","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2026/7/16 0:00:00","PubModel":"Epub","JCR":"Q2","JCRName":"INFECTIOUS DISEASES","Score":null,"Total":0}
引用次数: 0

Abstract

Objective: To assess whether wind-driven natural ventilation in the Infectious Diseases Treatment Module (IDTM) can achieve ventilation performance consistent with airborne precaution requirements [160 liters per second (L/s)] and to estimate associated pathogen-specific infection risks.

Methods: An experimental campaign of air velocity measurements and CO2 decays were conducted to validate the developed computational fluid dynamics (CFD) model. The validated CFD model simulated wind-driven natural ventilation (1-4 m/s) for an L-shaped IDTM configuration under four structural scenarios defined by the presence or absence of patient porches and mosquito nets. Airborne infection risk was estimated using a Wells-Riley quanta-based model for seven representative airborne pathogens under short-duration healthcare worker exposure and prolonged patient co-exposure.

Results: Ventilation performance varied widely based on wind speed and structural configuration. Airflow ranged from 7 L/s in the most restricted configuration (porch and mosquito nets present at 1 m/s) to over 3,100 L/s when mosquito nets were removed at 4 m/s.When mapped to infection-risk estimates, ventilation rates at 160 L/s substantially reduced short-duration healthcare worker infection risk for all pathogens (≤1%), whereas prolonged co-exposure remained associated with high risk for high-emission pathogens despite high ventilation.

Conclusion: Under favorable wind conditions and optimized configurations, the IDTM can achieve ventilation rates consistent with the 160 L/s recommendation for airborne precautions. While this provides substantial protection for healthcare workers, individual-room isolation remains essential for patient management. Operationally, removing window-mounted nets is the most effective way to ensure safety targets are met; hybrid ventilation measures should be considered during low-wind conditions.

可部署治疗设施中空气传播疾病管理的自然通风性能。
目的:评估传染病治疗模块(IDTM)的风力自然通风是否能达到符合空气传播预防要求[160升/秒(L/s)]的通风性能,并估计相关的病原体特异性感染风险。方法:进行了风速测量和CO2衰减的实验,以验证所开发的计算流体动力学(CFD)模型。经过验证的CFD模型模拟了l型IDTM配置在四种结构情景下的风驱动自然通风(1-4 m/s),这些结构情景由病人门廊和蚊帐的存在或不存在定义。使用Wells-Riley基于量子的模型,在医护人员短时间暴露和患者长时间共同暴露的情况下,对七种具有代表性的空气传播病原体进行空气传播感染风险估计。结果:通风性能随风速和结构形式的不同而变化很大。气流范围从最受限制的配置(门廊和蚊帐以1m /s的速度存在)的7 L/s到以4m /s的速度拆除蚊帐时的3100 L/s以上。当映射到感染风险估计时,160升/秒的通风率大大降低了所有病原体的短期感染风险(≤1%),而长时间的共同暴露仍然与高排放病原体的高风险相关,尽管高通风。结论:在良好的风条件和优化的配置下,IDTM的通风量符合空气传播预防建议的160 L/s。虽然这为医护人员提供了实质性的保护,但对患者管理来说,单独隔离病房仍然至关重要。在操作上,拆除安装在窗户上的网是确保达到安全目标的最有效方法;在低风条件下应考虑混合通风措施。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
CiteScore
6.40
自引率
6.70%
发文量
289
审稿时长
3-8 weeks
期刊介绍: Infection Control and Hospital Epidemiology provides original, peer-reviewed scientific articles for anyone involved with an infection control or epidemiology program in a hospital or healthcare facility. Written by infection control practitioners and epidemiologists and guided by an editorial board composed of the nation''s leaders in the field, ICHE provides a critical forum for this vital information.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书