{"title":"Faulty-Line Selection Method Based on Pearson Correlation Coefficient in Neutral Non-Effectively Grounded Systems","authors":"Yang Lei;Fan Yang;Yinjun Zhu;Jun Wang;Liuxin Xie;Jinghua Wang;Chao Wang;Heng Chen","doi":"10.23919/CJEE.2026.000005","DOIUrl":null,"url":null,"abstract":"When a single-phase grounded fault occurs in a distribution network, a quick selection of the faulty line is crucial for the safe and reliable operation of the network. To address the low accuracy of selection devices in detecting grounded faulty lines, a line selection method based on the Pearson correlation coefficient is proposed by analyzing the similarity of the zero-sequence current fitting curve and the slope curve of each line in the distribution network when a single-phase grounded fault occurs. The apparent difference between the slope of the zero-sequence current fitting curve of the faulty and healthy lines is used to select the faulty line. Specifically, a local weighted linear fitting and differentiation are performed on the zero-sequence currents of each line to obtain the corresponding slope curves. Subsequently, the similarity of the slope curves of the zero-sequence current waveforms of the adjacent lines is used to determine the faulty line. If the similarity between a line and two adjacent lines is poor or negative (Pearson correlation coefficient close to or less than 0), it is determined as a faulty line. If the similarity between a line and at least one adjacent line is high (Pearson correlation coefficient close to 1), it is determined to be a healthy line. If the similarity of the slope curves of the zero-sequence current waveform of all lines is high (Pearson correlation coefficient close to 1), it is determined to be a bus fault. Matlab/Simulink simulation results showed that the proposed method is effective under various fault conditions and has a high detection sensitivity to high transition resistance faults.","PeriodicalId":36428,"journal":{"name":"Chinese Journal of Electrical Engineering","volume":"12 2","pages":"299-310"},"PeriodicalIF":4.0000,"publicationDate":"2026-06-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=11603273","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Chinese Journal of Electrical Engineering","FirstCategoryId":"1087","ListUrlMain":"https://ieeexplore.ieee.org/document/11603273/","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2026/7/9 0:00:00","PubModel":"Epub","JCR":"Q1","JCRName":"Engineering","Score":null,"Total":0}
引用次数: 0
Abstract
When a single-phase grounded fault occurs in a distribution network, a quick selection of the faulty line is crucial for the safe and reliable operation of the network. To address the low accuracy of selection devices in detecting grounded faulty lines, a line selection method based on the Pearson correlation coefficient is proposed by analyzing the similarity of the zero-sequence current fitting curve and the slope curve of each line in the distribution network when a single-phase grounded fault occurs. The apparent difference between the slope of the zero-sequence current fitting curve of the faulty and healthy lines is used to select the faulty line. Specifically, a local weighted linear fitting and differentiation are performed on the zero-sequence currents of each line to obtain the corresponding slope curves. Subsequently, the similarity of the slope curves of the zero-sequence current waveforms of the adjacent lines is used to determine the faulty line. If the similarity between a line and two adjacent lines is poor or negative (Pearson correlation coefficient close to or less than 0), it is determined as a faulty line. If the similarity between a line and at least one adjacent line is high (Pearson correlation coefficient close to 1), it is determined to be a healthy line. If the similarity of the slope curves of the zero-sequence current waveform of all lines is high (Pearson correlation coefficient close to 1), it is determined to be a bus fault. Matlab/Simulink simulation results showed that the proposed method is effective under various fault conditions and has a high detection sensitivity to high transition resistance faults.