Transient Voltage Stability Assessment of Direct Current Multi-Infeed Receiving-End System Using Binary Table Criterion

IF 4 Q1 Engineering
Chinese Journal of Electrical Engineering Pub Date : 2026-06-01 Epub Date: 2026-07-09 DOI:10.23919/CJEE.2025.000189
Xintong Yang;Xiyu Yang;Peisheng Gao;Xinlong Jin;Jing Wang;Changjiang Wang
{"title":"Transient Voltage Stability Assessment of Direct Current Multi-Infeed Receiving-End System Using Binary Table Criterion","authors":"Xintong Yang;Xiyu Yang;Peisheng Gao;Xinlong Jin;Jing Wang;Changjiang Wang","doi":"10.23919/CJEE.2025.000189","DOIUrl":null,"url":null,"abstract":"Establishing a correlation between reactive power voltage dynamic characteristics and transient voltage stability (TVS) is essential for power system analysis. A TVS assessment method founded on a binary table criterion is introduced. Initially, the TVS state is depicted via a critical instability slip. A polynomial fitting approach is then employed to quantify the influence of multiple direct current (DC) control parameters on reactive power. This facilitates the explicit demonstration of how the reactive power dynamic characteristics of line-commutated converter-high-voltage direct current and voltage source converter-high-voltage direct current impact the critical instability slip within a DC multi-infeed receiving-end system. To achieve a quantitative description of the relationship linking DC control parameters to the post-fault TVS state, an index measuring the change rate of the critical instability slip is formulated. This index serves to characterize the TVS of the DC multi-infeed receiving-end system. The dynamic variations of the critical instability slip are quantitatively examined using a binary table, thereby providing a characterization of the TVS margin. By adaptively adjusting the weight based on the slip evolution process following a fault, a more precise and rational depiction of the TVS margin is achieved. Concluding the study, the efficacy and precision of the proposed methodology are validated through simulation analysis conducted on a modified IEEE-68 bus system.","PeriodicalId":36428,"journal":{"name":"Chinese Journal of Electrical Engineering","volume":"12 2","pages":"233-247"},"PeriodicalIF":4.0000,"publicationDate":"2026-06-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=11603270","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Chinese Journal of Electrical Engineering","FirstCategoryId":"1087","ListUrlMain":"https://ieeexplore.ieee.org/document/11603270/","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2026/7/9 0:00:00","PubModel":"Epub","JCR":"Q1","JCRName":"Engineering","Score":null,"Total":0}
引用次数: 0

Abstract

Establishing a correlation between reactive power voltage dynamic characteristics and transient voltage stability (TVS) is essential for power system analysis. A TVS assessment method founded on a binary table criterion is introduced. Initially, the TVS state is depicted via a critical instability slip. A polynomial fitting approach is then employed to quantify the influence of multiple direct current (DC) control parameters on reactive power. This facilitates the explicit demonstration of how the reactive power dynamic characteristics of line-commutated converter-high-voltage direct current and voltage source converter-high-voltage direct current impact the critical instability slip within a DC multi-infeed receiving-end system. To achieve a quantitative description of the relationship linking DC control parameters to the post-fault TVS state, an index measuring the change rate of the critical instability slip is formulated. This index serves to characterize the TVS of the DC multi-infeed receiving-end system. The dynamic variations of the critical instability slip are quantitatively examined using a binary table, thereby providing a characterization of the TVS margin. By adaptively adjusting the weight based on the slip evolution process following a fault, a more precise and rational depiction of the TVS margin is achieved. Concluding the study, the efficacy and precision of the proposed methodology are validated through simulation analysis conducted on a modified IEEE-68 bus system.
基于二值表准则的直流多馈接收端系统暂态电压稳定性评估
建立无功电压动态特性与暂态电压稳定性之间的关系是电力系统分析的重要内容。介绍了一种基于二值表准则的TVS评价方法。最初,TVS状态是通过临界不稳定性滑移来描述的。然后采用多项式拟合方法量化多个直流控制参数对无功功率的影响。这有助于明确演示线路换向变换器-高压直流和电压源变换器-高压直流的无功动态特性如何影响直流多馈入接收端系统的临界不稳定滑移。为了定量描述直流控制参数与故障后TVS状态之间的关系,建立了测量临界失稳滑差变化率的指标。该指标用于描述直流多馈入接收端系统的TVS特性。临界不稳定滑移的动态变化是用二值表定量地检验的,从而提供了TVS裕度的表征。通过根据断层后滑动演化过程自适应调整权值,获得了更精确、更合理的TVS裕度描述。最后,通过对改进的IEEE-68总线系统进行仿真分析,验证了所提方法的有效性和精度。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
Chinese Journal of Electrical Engineering
Chinese Journal of Electrical Engineering Energy-Energy Engineering and Power Technology
CiteScore
7.80
自引率
0.00%
发文量
621
审稿时长
12 weeks
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书