求助PDF
{"title":"Table-Lookup Estimation of Overvoltages at 275 kV Gas-Insulated Switchgears","authors":"Takashi Yamamoto, Toshihiro Tsuboi, Yoshihiro Baba","doi":"10.1002/tee.70235","DOIUrl":null,"url":null,"abstract":"<p>The lightning impulse withstand voltage (LIWV) of electric power equipment in substations has been determined and specified on the basis of lightning surge analyses. The lightning surge analysis needs a huge computation time and considerable expertise. In order to simplify the LIWV estimation, a table-lookup method based on parametric analyses of lightning surges conducted in advance was proposed for 275-kV transformers. In this study, lightning surge analyses of a 275-kV substation with gas-insulated switchgears (GISs) have been carried out to create a lookup table for estimating the LIWV of a 275-kV GIS. Evaluations for the correlation between parameters and required LIWV have been shown, and examples to use the table-lookup estimation have also been explained. © 2025 Institute of Electrical Engineers of Japan and Wiley Periodicals LLC.</p>","PeriodicalId":13435,"journal":{"name":"IEEJ Transactions on Electrical and Electronic Engineering","volume":"21 8","pages":"1179-1184"},"PeriodicalIF":1.0000,"publicationDate":"2026-07-02","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"IEEJ Transactions on Electrical and Electronic Engineering","FirstCategoryId":"5","ListUrlMain":"https://onlinelibrary.wiley.com/doi/10.1002/tee.70235","RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"2025/12/22 0:00:00","PubModel":"Epub","JCR":"Q4","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 0
引用
批量引用
Abstract
The lightning impulse withstand voltage (LIWV) of electric power equipment in substations has been determined and specified on the basis of lightning surge analyses. The lightning surge analysis needs a huge computation time and considerable expertise. In order to simplify the LIWV estimation, a table-lookup method based on parametric analyses of lightning surges conducted in advance was proposed for 275-kV transformers. In this study, lightning surge analyses of a 275-kV substation with gas-insulated switchgears (GISs) have been carried out to create a lookup table for estimating the LIWV of a 275-kV GIS. Evaluations for the correlation between parameters and required LIWV have been shown, and examples to use the table-lookup estimation have also been explained. © 2025 Institute of Electrical Engineers of Japan and Wiley Periodicals LLC.
275kv气体绝缘开关设备过电压的表查找估计
在分析雷电浪涌的基础上,确定并规定了变电站电力设备的耐雷击电压。雷电浪涌分析需要大量的计算时间和大量的专业知识。为了简化LIWV的估计,提出了一种基于预先进行的雷击浪涌参数分析的查找表方法。在本研究中,对一个275千伏气体绝缘开关设备(GISs)的变电站进行了雷击浪涌分析,以创建一个查找表,用于估计275千伏地理信息系统的LIWV。已经展示了参数和所需LIWV之间的相关性的评估,并且还解释了使用表查找估计的示例。©2025日本电气工程师协会和Wiley期刊有限责任公司。
本文章由计算机程序翻译,如有差异,请以英文原文为准。