{"title":"Development and Validation of Estimation of Breakdown Voltage of Stator Windings of Generator From Partial Discharge Magnitude","authors":"Shin Nakamura, Masaki Kanegami, Takashi Kuraishi, Satoru Miyazaki","doi":"10.1002/eej.23489","DOIUrl":null,"url":null,"abstract":"<div>\n \n <p>For the insulation diagnosis of stator windings of generators, sampling surveys are conducted on the coils to estimate the dielectric strength of the stator winding. Previous research has relied on inferring the breakdown voltage of the stator winding from the value 3σ away from the mean value of the breakdown voltage of the coil. However, this conventional method exhibits a significant estimation error when the sample size is small. Therefore, we propose a method for estimating the breakdown voltage of the stator winding based on the maximum value of the partial discharge magnitude and the minimum value of the breakdown voltage of the sample coil. We verify this method by Monte Carlo simulation assuming a sampling survey of coils.</p>\n </div>","PeriodicalId":50550,"journal":{"name":"Electrical Engineering in Japan","volume":"218 1","pages":""},"PeriodicalIF":0.4000,"publicationDate":"2025-01-06","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Electrical Engineering in Japan","FirstCategoryId":"5","ListUrlMain":"https://onlinelibrary.wiley.com/doi/10.1002/eej.23489","RegionNum":4,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q4","JCRName":"ENGINEERING, ELECTRICAL & ELECTRONIC","Score":null,"Total":0}
引用次数: 0
Abstract
For the insulation diagnosis of stator windings of generators, sampling surveys are conducted on the coils to estimate the dielectric strength of the stator winding. Previous research has relied on inferring the breakdown voltage of the stator winding from the value 3σ away from the mean value of the breakdown voltage of the coil. However, this conventional method exhibits a significant estimation error when the sample size is small. Therefore, we propose a method for estimating the breakdown voltage of the stator winding based on the maximum value of the partial discharge magnitude and the minimum value of the breakdown voltage of the sample coil. We verify this method by Monte Carlo simulation assuming a sampling survey of coils.
期刊介绍:
Electrical Engineering in Japan (EEJ) is an official journal of the Institute of Electrical Engineers of Japan (IEEJ). This authoritative journal is a translation of the Transactions of the Institute of Electrical Engineers of Japan. It publishes 16 issues a year on original research findings in Electrical Engineering with special focus on the science, technology and applications of electric power, such as power generation, transmission and conversion, electric railways (including magnetic levitation devices), motors, switching, power economics.