Experimental behavior of prestressed concrete beams under simultaneous sustained loading and corrosion

IF 3 3区 工程技术 Q2 CONSTRUCTION & BUILDING TECHNOLOGY
Fabio Di Carlo, Zila Rinaldi, Alberto Meda, Filippo Molaioni
{"title":"Experimental behavior of prestressed concrete beams under simultaneous sustained loading and corrosion","authors":"Fabio Di Carlo, Zila Rinaldi, Alberto Meda, Filippo Molaioni","doi":"10.1002/suco.202400304","DOIUrl":null,"url":null,"abstract":"The paper presents an experimental study for the evaluation of the flexural response and failure mode of a prestressed concrete (PC) beam subjected to simultaneous sustained loads and corrosion. The obtained results are judged and discussed also through a comparison with the experimental outcomes on a reference sound PC beam, and a companion specimen subjected to artificial corrosion first, and then tested in bending. The three specimens are characterized by a 200 × 300 mm rectangular cross section, a total length of 3700 mm, and a clear span of 2700 mm. The value of the sustained load, applied with a simultaneous accelerated corrosion process of the strands, was chosen, based on the result of the uncorroded reference beam, to achieve a scenario that can occur in a real structure in situ. The flexural response of the tested element was monitored over a period of 70 days, up to failure, and showed to be highly dependent on the localization of the corrosion phenomena affecting the strands, especially when coinciding with the maximum bending moment position. The obtained results are finally compared with the ones obtained on a PC beam with the same geometry and material properties, first subjected to corrosion and then tested in bending. The differences in corrosion morphology and location and in the failure mode of the strand confirm the importance of accounting for the combined effect of reinforcement corrosion and loading when assessing the structural performance of PC beams.","PeriodicalId":21988,"journal":{"name":"Structural Concrete","volume":"12 1","pages":""},"PeriodicalIF":3.0000,"publicationDate":"2024-07-25","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Structural Concrete","FirstCategoryId":"5","ListUrlMain":"https://doi.org/10.1002/suco.202400304","RegionNum":3,"RegionCategory":"工程技术","ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"Q2","JCRName":"CONSTRUCTION & BUILDING TECHNOLOGY","Score":null,"Total":0}
引用次数: 0

Abstract

The paper presents an experimental study for the evaluation of the flexural response and failure mode of a prestressed concrete (PC) beam subjected to simultaneous sustained loads and corrosion. The obtained results are judged and discussed also through a comparison with the experimental outcomes on a reference sound PC beam, and a companion specimen subjected to artificial corrosion first, and then tested in bending. The three specimens are characterized by a 200 × 300 mm rectangular cross section, a total length of 3700 mm, and a clear span of 2700 mm. The value of the sustained load, applied with a simultaneous accelerated corrosion process of the strands, was chosen, based on the result of the uncorroded reference beam, to achieve a scenario that can occur in a real structure in situ. The flexural response of the tested element was monitored over a period of 70 days, up to failure, and showed to be highly dependent on the localization of the corrosion phenomena affecting the strands, especially when coinciding with the maximum bending moment position. The obtained results are finally compared with the ones obtained on a PC beam with the same geometry and material properties, first subjected to corrosion and then tested in bending. The differences in corrosion morphology and location and in the failure mode of the strand confirm the importance of accounting for the combined effect of reinforcement corrosion and loading when assessing the structural performance of PC beams.
预应力混凝土梁在持续荷载和腐蚀同时作用下的实验行为
本文介绍了一项实验研究,用于评估预应力混凝土(PC)梁在同时承受持续荷载和腐蚀的情况下的弯曲响应和破坏模式。本文还通过与参照健全 PC 梁的实验结果以及先进行人工腐蚀然后再进行弯曲测试的同伴试样进行比较,对所获得的结果进行了判断和讨论。这三个试样的横截面为 200 × 300 毫米的矩形,总长度为 3700 毫米,净跨度为 2700 毫米。在对钢绞线进行加速腐蚀的同时施加的持续荷载值是根据未腐蚀参考梁的结果选定的,以实现在实际结构中可能发生的情况。在 70 天的时间里,对受测元件的弯曲响应进行了监测,直至其失效,结果表明,这种响应与影响钢绞线的腐蚀现象的局部性有很大关系,尤其是与最大弯矩位置相吻合时。最后,将所获得的结果与在具有相同几何形状和材料特性的 PC 梁上获得的结果进行了比较,后者首先受到腐蚀,然后进行了弯曲测试。腐蚀形态和位置以及钢绞线破坏模式的差异证明,在评估 PC 梁的结构性能时,考虑钢筋腐蚀和荷载的综合影响非常重要。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
Structural Concrete
Structural Concrete CONSTRUCTION & BUILDING TECHNOLOGY-ENGINEERING, CIVIL
CiteScore
5.60
自引率
15.60%
发文量
284
审稿时长
3 months
期刊介绍: Structural Concrete, the official journal of the fib, provides conceptual and procedural guidance in the field of concrete construction, and features peer-reviewed papers, keynote research and industry news covering all aspects of the design, construction, performance in service and demolition of concrete structures. Main topics: design, construction, performance in service, conservation (assessment, maintenance, strengthening) and demolition of concrete structures research about the behaviour of concrete structures development of design methods fib Model Code sustainability of concrete structures.
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信