Audit Kelistrikan pada Gedung Administrasi Niaga (AB) dan Akuntansi (AC) Politeknik Negeri Malang

Ahmad Hermawan, Roby Tri Stya Hutama, Budi Eko Prasetyo, Candra Wiharya
{"title":"Audit Kelistrikan pada Gedung Administrasi Niaga (AB) dan Akuntansi (AC) Politeknik Negeri Malang","authors":"Ahmad Hermawan, Roby Tri Stya Hutama, Budi Eko Prasetyo, Candra Wiharya","doi":"10.33795/elposys.v8i1.620","DOIUrl":null,"url":null,"abstract":"This study aims to analyze the average consumption of electrical energy and the Intensity of Energy Consumption (IKE)and the effect of temperature of electrical equipment in the main panel of the AB and AC buildings on the applicable electrical standards in the AB and AC buildings of Politeknik Negeri Malang. From the research, the results of the average consumption of electrical energy in each building are 2591.96 kWh and 1799.74 kWh per month, the value of Energy Consumption Intensity (IKE) is 34.55 kWh / m2 and 34.11 kWh / m2, both results fall into the category of energy use. very efficient, all the equipment in the panels of the two buildings is in good condition according to the PLN SK DIR 520 2014 book, the highest temperature value of the safety equipment is 32.8 ᵒC at NH Fuse T. this is due to the current flowing of 34.29A, the value of the equipment with the lowest temperature of 27.8 C on MCB C16 with a maximum standard of 45 C, the current conductive capacity is still in accordance with using a 2.5 mm2 cable with KHA 46 A, while the load current for each branch is protected by MCB 10 A. For cooling in rooms that use AC The split is 28,000 BTU / hour and it is still below the standard of 38,000 BTU / hour","PeriodicalId":476257,"journal":{"name":"Elposys: Jurnal Sistem Kelistrikan","volume":"518 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2023-02-15","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Elposys: Jurnal Sistem Kelistrikan","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.33795/elposys.v8i1.620","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

This study aims to analyze the average consumption of electrical energy and the Intensity of Energy Consumption (IKE)and the effect of temperature of electrical equipment in the main panel of the AB and AC buildings on the applicable electrical standards in the AB and AC buildings of Politeknik Negeri Malang. From the research, the results of the average consumption of electrical energy in each building are 2591.96 kWh and 1799.74 kWh per month, the value of Energy Consumption Intensity (IKE) is 34.55 kWh / m2 and 34.11 kWh / m2, both results fall into the category of energy use. very efficient, all the equipment in the panels of the two buildings is in good condition according to the PLN SK DIR 520 2014 book, the highest temperature value of the safety equipment is 32.8 ᵒC at NH Fuse T. this is due to the current flowing of 34.29A, the value of the equipment with the lowest temperature of 27.8 C on MCB C16 with a maximum standard of 45 C, the current conductive capacity is still in accordance with using a 2.5 mm2 cable with KHA 46 A, while the load current for each branch is protected by MCB 10 A. For cooling in rooms that use AC The split is 28,000 BTU / hour and it is still below the standard of 38,000 BTU / hour
商业行政大楼(AB)和会计(AC)政治学方面的电力审计
本研究旨在分析耐玛琅理工大学空调建筑的平均电能消耗和能耗强度(IKE),以及空调建筑主面板电气设备温度对空调建筑适用电气标准的影响。从研究结果来看,每栋建筑每月平均消耗电能分别为2591.96 kWh和1799.74 kWh,能耗强度(IKE)值分别为34.55 kWh / m2和34.11 kWh / m2,均属于能源使用范畴。非常有效,所有的设备面板的两个建筑完好根据PLN SK DIR 520 2014本书,安全设备的最高温度的值是32.8ᵒC在NH保险丝t .这是由于电流34.29 a的值最低的设备温度27.8摄氏度的MCB C16最多45度标准,目前的导电能力仍然是按照用2.5平方毫米的电缆KHA 46,而每个支路的负载电流由小断路器10a保护。对于使用交流空调的房间,分值为28000 BTU /小时,仍低于38000 BTU /小时的标准
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信