Computation of very fast transient overvoltages (VFTO) in a 1000 kV gas insulated substation

M. Haseeb, M. J. Thomas
{"title":"Computation of very fast transient overvoltages (VFTO) in a 1000 kV gas insulated substation","authors":"M. Haseeb, M. J. Thomas","doi":"10.1109/APPEEC.2017.8308964","DOIUrl":null,"url":null,"abstract":"Very fast transient overvoltages (VFTO) generated in a gas insulated substation (GIS) during disconnector switching operations is one of the major concerns in insulation design of the GIS. Such over voltages can cause malfunctioning of the protection and control circuits in addition to initiating faults inside the gas insulated bus ducts of the substation especially in the presence of metallic particles. In this paper, VFTO have been estimated at various points in a 1000 kV rated substation for all possible valid disconnector switching operations. For the substation studied, the maximum computed overvoltage is 1.58 pu without considering the trapped charge on the busbar. Major frequency components in the simulated VFTO lies in the range of 840 KHz to 30 MHz. Simulations have been carried out using the Electromagnetic Transient Program (EMTP).","PeriodicalId":247669,"journal":{"name":"2017 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC)","volume":"30 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2017-11-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2017 IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/APPEEC.2017.8308964","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2

Abstract

Very fast transient overvoltages (VFTO) generated in a gas insulated substation (GIS) during disconnector switching operations is one of the major concerns in insulation design of the GIS. Such over voltages can cause malfunctioning of the protection and control circuits in addition to initiating faults inside the gas insulated bus ducts of the substation especially in the presence of metallic particles. In this paper, VFTO have been estimated at various points in a 1000 kV rated substation for all possible valid disconnector switching operations. For the substation studied, the maximum computed overvoltage is 1.58 pu without considering the trapped charge on the busbar. Major frequency components in the simulated VFTO lies in the range of 840 KHz to 30 MHz. Simulations have been carried out using the Electromagnetic Transient Program (EMTP).
1000kv气体绝缘变电站快速瞬态过电压的计算
气体绝缘变电站(GIS)在隔离开关操作过程中产生的快速瞬态过电压(VFTO)是GIS绝缘设计中的主要问题之一。这种过电压除了引起变电站气体绝缘母线管道内的故障外,还会引起保护和控制电路的故障,特别是在存在金属颗粒的情况下。在本文中,在1000千伏额定变电站的各个点上,对所有可能的有效隔离开关操作进行了VFTO估计。对于所研究的变电站,在不考虑母线上捕获电荷的情况下,计算出的最大过电压为1.58 pu。在模拟的VFTO中,主要的频率分量位于840 KHz到30 MHz的范围内。利用电磁瞬变程序(EMTP)进行了仿真。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信