Linear Trend Application on the Estimated Age of Distribution Transformer Based on the Load Growth and Environmental Temperature

F. Azhar, Y. Rahmawati, I. Fadlika
{"title":"Linear Trend Application on the Estimated Age of Distribution Transformer Based on the Load Growth and Environmental Temperature","authors":"F. Azhar, Y. Rahmawati, I. Fadlika","doi":"10.17977/um049v1i2p7-12","DOIUrl":null,"url":null,"abstract":"This research aimed to find the age loss of distribution transformer based on the load growth and ambient temperature to predict the remaining age of the transformer. This research used the remaining estimation age calculation based on load growth that was predicted using the linear trend analysis. The distribution transformer in this research was the BO043 200 kVA, installed in 2012, and was operated in Bolo Feeder, Woha District, Bima Regency. The results showed that the BO043 transformer was operating at the average ambient temperature of 28℃ with the optimum loading threshold of 92.77% from its power rating. The transformer would experience age reduction if the load given were above that value. The calculation results showed that the BO043 transformer had the estimated remaining age of 4 years from the standard 23 years with the 2019 load prediction of 83.39% and up to 115.94% load prediction in 2022.","PeriodicalId":285860,"journal":{"name":"Frontier Energy System and Power Engineering","volume":"28 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2019-07-26","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Frontier Energy System and Power Engineering","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.17977/um049v1i2p7-12","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

This research aimed to find the age loss of distribution transformer based on the load growth and ambient temperature to predict the remaining age of the transformer. This research used the remaining estimation age calculation based on load growth that was predicted using the linear trend analysis. The distribution transformer in this research was the BO043 200 kVA, installed in 2012, and was operated in Bolo Feeder, Woha District, Bima Regency. The results showed that the BO043 transformer was operating at the average ambient temperature of 28℃ with the optimum loading threshold of 92.77% from its power rating. The transformer would experience age reduction if the load given were above that value. The calculation results showed that the BO043 transformer had the estimated remaining age of 4 years from the standard 23 years with the 2019 load prediction of 83.39% and up to 115.94% load prediction in 2022.
基于负荷增长和环境温度的配电变压器寿命估计的线性趋势应用
本研究旨在根据负荷增长和环境温度计算配电变压器的龄损,以预测配电变压器的剩余龄。本研究使用基于负荷增长的剩余估计年龄计算,并使用线性趋势分析预测负荷增长。本研究的配电变压器为BO043 200kva,安装于2012年,运行于Bima县Woha区Bolo Feeder。结果表明,BO043变压器在平均环境温度为28℃时运行,其额定功率的最佳负载阈值为92.77%。如果给定的负载高于该值,则变压器将经历老化。计算结果表明,BO043变压器在标准23年的基础上,预计剩余寿命为4年,2019年负荷预测率为83.39%,2022年负荷预测率高达115.94%。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信