Analysis of XLPE Cable Health Assessment Parameters under Various Test Voltages by PDC Method

C. Suo, H. Yi, Y. Zhang, A. C. Yucel, K. W. Tan, H. Gooi, C. T. Wee, W. K. Chern, A. Ghias
{"title":"Analysis of XLPE Cable Health Assessment Parameters under Various Test Voltages by PDC Method","authors":"C. Suo, H. Yi, Y. Zhang, A. C. Yucel, K. W. Tan, H. Gooi, C. T. Wee, W. K. Chern, A. Ghias","doi":"10.1109/ICHVE53725.2022.9961371","DOIUrl":null,"url":null,"abstract":"Cross-linked polyethylene (XLPE) has been widely used as an insulation material in power cables because of its superior electrical characteristics. The measurement of polarization and depolarization current (PDC) is a classical method used to study the health states of XLPE cables. This paper studied the effects of test voltage on the PDC measurement results and assessment parameters calculated results. The PDC tests of one new and one old cable were carried out under 2kV to 6kV with an interval of 1kV. The assessment parameters such as insulation resistance (IR), polarization index (PI), dielectric absorption ratio (DAR), dielectric loss tan δ, and ageing factor were calculated and analyzed. The results show that with the increase of test voltage, all the assessment parameters are almost independent to the test voltage for the new cable. However, for the old cable, the IR, DAR, and PI values decrease, and tan δ increase with test voltage.","PeriodicalId":125983,"journal":{"name":"2022 IEEE International Conference on High Voltage Engineering and Applications (ICHVE)","volume":"69 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2022-09-25","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2022 IEEE International Conference on High Voltage Engineering and Applications (ICHVE)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICHVE53725.2022.9961371","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

Cross-linked polyethylene (XLPE) has been widely used as an insulation material in power cables because of its superior electrical characteristics. The measurement of polarization and depolarization current (PDC) is a classical method used to study the health states of XLPE cables. This paper studied the effects of test voltage on the PDC measurement results and assessment parameters calculated results. The PDC tests of one new and one old cable were carried out under 2kV to 6kV with an interval of 1kV. The assessment parameters such as insulation resistance (IR), polarization index (PI), dielectric absorption ratio (DAR), dielectric loss tan δ, and ageing factor were calculated and analyzed. The results show that with the increase of test voltage, all the assessment parameters are almost independent to the test voltage for the new cable. However, for the old cable, the IR, DAR, and PI values decrease, and tan δ increase with test voltage.
用PDC法分析不同试验电压下交联聚乙烯电缆健康评估参数
交联聚乙烯(XLPE)由于其优越的电气特性,被广泛用作电力电缆的绝缘材料。测量交联聚乙烯电缆的极化和去极化电流(PDC)是研究交联聚乙烯电缆健康状态的经典方法。本文研究了试验电压对PDC测量结果和评估参数计算结果的影响。在2kV ~ 6kV条件下,以1kV为间隔,分别对1条新电缆和1条旧电缆进行PDC试验。计算并分析了绝缘电阻(IR)、极化指数(PI)、介电吸收比(DAR)、介电损耗tan δ和老化因子等评价参数。结果表明,随着试验电压的升高,新电缆的所有评价参数与试验电压基本无关。然而,对于旧电缆,随着测试电压的增加,IR、DAR和PI值降低,tan δ增加。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信