The theory of CT saturation detection based on virtual impedance in bus-bar differential protection

Yongbin Zhao, Yuping Lu
{"title":"The theory of CT saturation detection based on virtual impedance in bus-bar differential protection","authors":"Yongbin Zhao, Yuping Lu","doi":"10.1109/POWERI.2006.1632527","DOIUrl":null,"url":null,"abstract":"The serious short circuit current may possibly lead to current transformer (CT) saturation. If the CT saturates in an external fault, the bus-bar differential protection may operate incorrectly. Most bus-bar differential relays use low-impedance criterion to detect CT saturation to avoid false tripping for a nearby external fault. It is very important research direction for accurately detecting CT saturation in bus-bar differential protection. Analyzing CT saturation detection methods of the current waveform, the variety of differential current, harmonic ratio, and so on, these methods are not best solutions for serious CT saturation. The paper proposed a new method for CT saturation detection. The method is to suppose a virtual impedance branch to the power bus bar, then to calculate the value changes in the virtual impedance with the transmission line RL integral model, to detect CT saturation when an external or internal fault occurs","PeriodicalId":191301,"journal":{"name":"2006 IEEE Power India Conference","volume":"80 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2006-06-05","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2006 IEEE Power India Conference","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/POWERI.2006.1632527","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

The serious short circuit current may possibly lead to current transformer (CT) saturation. If the CT saturates in an external fault, the bus-bar differential protection may operate incorrectly. Most bus-bar differential relays use low-impedance criterion to detect CT saturation to avoid false tripping for a nearby external fault. It is very important research direction for accurately detecting CT saturation in bus-bar differential protection. Analyzing CT saturation detection methods of the current waveform, the variety of differential current, harmonic ratio, and so on, these methods are not best solutions for serious CT saturation. The paper proposed a new method for CT saturation detection. The method is to suppose a virtual impedance branch to the power bus bar, then to calculate the value changes in the virtual impedance with the transmission line RL integral model, to detect CT saturation when an external or internal fault occurs
母线差动保护中基于虚阻抗的CT饱和检测原理
严重的短路电流可能导致电流互感器饱和。如果CT在外部故障时饱和,可能导致母线差动保护工作不正常。大多数母线差分继电器使用低阻抗判据来检测CT饱和,以避免附近外部故障的误跳闸。在母线差动保护中准确检测CT饱和是非常重要的研究方向。分析了CT饱和检测方法的电流波形、差动电流的变化、谐波比等,这些方法都不是解决CT严重饱和的最佳方法。提出了一种新的CT饱和度检测方法。该方法是在电源母线上假设一个虚拟阻抗支路,然后利用传输线RL积分模型计算虚拟阻抗的值变化,检测发生外部或内部故障时的CT饱和
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信