Correlation between Voltage Endurance and Dielectric Loss Tangent/Partial Discharge for Stator Coils of HV Motors

Haiyang Ren, Songlin Jiang, Qinxue Yu, Jiaxi He, L. Zhong
{"title":"Correlation between Voltage Endurance and Dielectric Loss Tangent/Partial Discharge for Stator Coils of HV Motors","authors":"Haiyang Ren, Songlin Jiang, Qinxue Yu, Jiaxi He, L. Zhong","doi":"10.1109/CEIDP49254.2020.9437526","DOIUrl":null,"url":null,"abstract":"Vacuum pressure impregnation (VPI) technique is now widely used in the insulation systems of high voltage (HV) motors and generators due to good electrical, mechanical and thermal performances. The voltage endurance, dielectric loss tangent and partial discharge are the most common and effective means to assess the electrical properties of full-size stator coils. In this paper, the relationship between voltage endurance and tanδ as well as the partial discharge is investigated for stator coils with the rated voltage (Un) of 10kV. The voltage endurance test is carried out at 3Un50Hz. The tanδ measurement is performed over the voltage range of 0.2 Un- 1.2 Un with intervals of 0.2Un. Partial discharge is measured to obtain the inception voltage, extinction voltage and QIECvalues in the operating voltage (Un/√3) and the rated voltage (Un). It has been found that the coil group with longer voltage endurance tends to show lower tanδ and tip-up, higher inception and extinction voltages and smaller apparent partial charges. It manifests that the destructive voltage endurance test and non-destructive diagnostic measurements of tanδ and partial discharge have good consistency in assessing the insulation properties for HV coils. Moreover, calculations of correlation coefficients between voltage endurance and tanδ or partial discharge parameters show that the tanδ and partial discharge magnitude at the operating voltage can be more effective for evaluating the quality and estimating the lifetime of insulation system for HV coils, compared with such parameters measured at the rated voltage.","PeriodicalId":170813,"journal":{"name":"2020 IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP)","volume":"707 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2020-10-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2020 IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CEIDP49254.2020.9437526","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

Vacuum pressure impregnation (VPI) technique is now widely used in the insulation systems of high voltage (HV) motors and generators due to good electrical, mechanical and thermal performances. The voltage endurance, dielectric loss tangent and partial discharge are the most common and effective means to assess the electrical properties of full-size stator coils. In this paper, the relationship between voltage endurance and tanδ as well as the partial discharge is investigated for stator coils with the rated voltage (Un) of 10kV. The voltage endurance test is carried out at 3Un50Hz. The tanδ measurement is performed over the voltage range of 0.2 Un- 1.2 Un with intervals of 0.2Un. Partial discharge is measured to obtain the inception voltage, extinction voltage and QIECvalues in the operating voltage (Un/√3) and the rated voltage (Un). It has been found that the coil group with longer voltage endurance tends to show lower tanδ and tip-up, higher inception and extinction voltages and smaller apparent partial charges. It manifests that the destructive voltage endurance test and non-destructive diagnostic measurements of tanδ and partial discharge have good consistency in assessing the insulation properties for HV coils. Moreover, calculations of correlation coefficients between voltage endurance and tanδ or partial discharge parameters show that the tanδ and partial discharge magnitude at the operating voltage can be more effective for evaluating the quality and estimating the lifetime of insulation system for HV coils, compared with such parameters measured at the rated voltage.
高压电机定子线圈介电损耗与正切/局部放电的关系
真空压力浸渍(VPI)技术由于其良好的电气、机械和热工性能,在高压电机和发电机的绝缘系统中得到了广泛的应用。电压耐久、介电损耗正切和局部放电是评估大尺寸定子线圈电性能最常用、最有效的方法。本文研究了定子线圈额定电压为10kV时,电压耐久度与tanδ及局部放电的关系。在3Un50Hz下进行耐压试验。tanδ测量在0.2Un - 1.2 Un的电压范围内进行,间隔为0.2Un。测量局部放电,得到工作电压(Un/√3)和额定电压(Un)下的起始电压、消光电压和qiec值。结果表明,耐压时间越长的线圈组具有较低的tanδ和tip-up,较高的起始电压和消光电压以及较小的表观部分电荷。试验结果表明,破坏性耐压试验和局部放电无损诊断方法在评价高压线圈绝缘性能方面具有良好的一致性。此外,电压耐久性与tanδ或局部放电参数之间的相关系数计算表明,与在额定电压下测量的tanδ和局部放电大小相比,工作电压下的tanδ和局部放电大小可以更有效地评估高压线圈绝缘系统的质量和寿命。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信