Comparing transformer derating computed using the harmonic loss factor FHL and K-factor

Tao Shun, Xiao Xiangning
{"title":"Comparing transformer derating computed using the harmonic loss factor FHL and K-factor","authors":"Tao Shun, Xiao Xiangning","doi":"10.1109/DRPT.2008.4523666","DOIUrl":null,"url":null,"abstract":"The transformer losses will increase while it is supplying nonlinear load current. The derating measure for normal transformers is always taken to limit the temperature of windings or top-oil. In this paper, the formulations how to calculate the maximum permissible rms non-sinusoidal load current (Imax) using the harmonic loss factors FHL and K-factor were introduced. The difference of them was also reasoned and a case study illustrated the process of reasoning. The applications of these two factors were discussed too. Imax computed using FHL for normal transformer is more economical because Imax computed using K-factor is more conservative. Based on the actual monitoring data of harmonic component, K-factor is suitable for selecting right transformers in design and FHL for establishing transformers operation capability, therefore there is a harmonic loss margin when the transformers supply non-sinusoidal load.","PeriodicalId":240420,"journal":{"name":"2008 Third International Conference on Electric Utility Deregulation and Restructuring and Power Technologies","volume":"5 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2008-04-06","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"19","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2008 Third International Conference on Electric Utility Deregulation and Restructuring and Power Technologies","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/DRPT.2008.4523666","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 19

Abstract

The transformer losses will increase while it is supplying nonlinear load current. The derating measure for normal transformers is always taken to limit the temperature of windings or top-oil. In this paper, the formulations how to calculate the maximum permissible rms non-sinusoidal load current (Imax) using the harmonic loss factors FHL and K-factor were introduced. The difference of them was also reasoned and a case study illustrated the process of reasoning. The applications of these two factors were discussed too. Imax computed using FHL for normal transformer is more economical because Imax computed using K-factor is more conservative. Based on the actual monitoring data of harmonic component, K-factor is suitable for selecting right transformers in design and FHL for establishing transformers operation capability, therefore there is a harmonic loss margin when the transformers supply non-sinusoidal load.
比较用谐波损耗因子FHL和k因子计算的变压器降额
变压器在提供非线性负载电流时,损耗会增大。普通变压器的降额措施通常是为了限制绕组或顶部油的温度。本文介绍了利用谐波损耗因子FHL和k因子计算最大允许有效值非正弦负载电流(Imax)的公式。对两者的差异进行了分析,并通过实例说明了分析的过程。讨论了这两种因素的应用。由于使用k因子计算的Imax更为保守,因此用FHL计算普通变压器的Imax更为经济。根据谐波分量的实际监测数据,k因子适用于设计中选择合适的变压器,适用于建立变压器运行能力的FHL,因此变压器在供电非正弦负荷时存在谐波损耗裕度。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信