L. F. de F Gutierres, L. Mariotto, G. Cardoso, F. Loose
{"title":"Recloser-fuse coordination protection for inverter-based distributed generation systems","authors":"L. F. de F Gutierres, L. Mariotto, G. Cardoso, F. Loose","doi":"10.1109/UPEC.2015.7339778","DOIUrl":null,"url":null,"abstract":"This paper presents a novel recloser-fuse coordination protection for inverter-based distributed generation systems based on the use of RMS current comparators. In real-time, these comparators are responsible for analyzing current magnitude in upstream and downstream network directions; identify faults; and assess the recloser-fuse coordination status based on critical margins identified by the protection methodology. Once a mis-coordination is detected, some distributed generation units are strategically disconnected from the distribution network by gate turn-off thyristors. As a result of this action, short-circuit current is reduced to a satisfactory level, restoring the coordination between recloser and fuses in the grid. The proposed methodology has been implemented in a 12.47-kV grid with interconnection of 10 MW and 15 MW wind farms. Simulations have been carried out in ATP/EMTP. Significantly, the approach contributes to the adequacy and modernization of distribution systems with considerable tendency of distributed generation insertion.","PeriodicalId":446482,"journal":{"name":"2015 50th International Universities Power Engineering Conference (UPEC)","volume":"115 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2015-12-03","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2015 50th International Universities Power Engineering Conference (UPEC)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/UPEC.2015.7339778","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
Abstract
This paper presents a novel recloser-fuse coordination protection for inverter-based distributed generation systems based on the use of RMS current comparators. In real-time, these comparators are responsible for analyzing current magnitude in upstream and downstream network directions; identify faults; and assess the recloser-fuse coordination status based on critical margins identified by the protection methodology. Once a mis-coordination is detected, some distributed generation units are strategically disconnected from the distribution network by gate turn-off thyristors. As a result of this action, short-circuit current is reduced to a satisfactory level, restoring the coordination between recloser and fuses in the grid. The proposed methodology has been implemented in a 12.47-kV grid with interconnection of 10 MW and 15 MW wind farms. Simulations have been carried out in ATP/EMTP. Significantly, the approach contributes to the adequacy and modernization of distribution systems with considerable tendency of distributed generation insertion.