Tripping Profile Analysis of the 33 kV Feeder of Ugbowo 2 x 15 MVA, 33/11 kV Injection Substation

F. O. Akpojedje, Y. O. Abu, Onoriode Onowighose
{"title":"Tripping Profile Analysis of the 33 kV Feeder of Ugbowo 2 x 15 MVA, 33/11 kV Injection Substation","authors":"F. O. Akpojedje, Y. O. Abu, Onoriode Onowighose","doi":"10.4314/equijost.v8i1.3","DOIUrl":null,"url":null,"abstract":"This paper investigated the tripping profile of the 33 kV feeder of Ugbowo 2 x 15 MVA, 33/11 kV electric powerdistribution network. The annual data of daily tripping of the 33 kV feeder from September 2019 to August 2020were collated and collected from the Ugbowo injection substation. The daily outage of the 33 kV feeder was usedto compute the monthly and yearly tripping profile of the sub-transmission line (33 kV feeder) of the Ugbowoinjection substation. The monthly and yearly failure rate, MTTR, MTTF, MTBF, availability, unavailability, SAIFI,SAIDI, ASAI, ASUI, etc. for the period of twelve (12) months were analyzed using the Load Point Indices (LPI)and Microsoft Excel was used graphically to interpret the results of the tripping profile of the 33 kV feeder. Theresults obtained from the analyses of the 33 kV feeder of the network showed that yearly failure rate, MTTR,MTTF, MTBF, unavailability, availability, SAIFI, SAIDI, ASAI and ASUI were 4.32%, 6.520 h, 23.148 h, 29.668h, 21.98%, 78.02%, 0.0358 interruptions/customer/yr, 0.2336 h/customer/yr, 78.03%, and 21.97%, respectively.These results revealed that the performance indices of the 33 kV feeder with annual total outage frequency (SAIFI)and percentage availability (ASAI) were a far cry from the recommended values of the internationally acceptablestandard value (IASV) of 0.01 and 99.99% respectively. This poses a threat to the reliability and availability ofelectricity supply to consumers.","PeriodicalId":158544,"journal":{"name":"Equity Journal of Science and Technology","volume":"58 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2022-04-18","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Equity Journal of Science and Technology","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.4314/equijost.v8i1.3","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

This paper investigated the tripping profile of the 33 kV feeder of Ugbowo 2 x 15 MVA, 33/11 kV electric powerdistribution network. The annual data of daily tripping of the 33 kV feeder from September 2019 to August 2020were collated and collected from the Ugbowo injection substation. The daily outage of the 33 kV feeder was usedto compute the monthly and yearly tripping profile of the sub-transmission line (33 kV feeder) of the Ugbowoinjection substation. The monthly and yearly failure rate, MTTR, MTTF, MTBF, availability, unavailability, SAIFI,SAIDI, ASAI, ASUI, etc. for the period of twelve (12) months were analyzed using the Load Point Indices (LPI)and Microsoft Excel was used graphically to interpret the results of the tripping profile of the 33 kV feeder. Theresults obtained from the analyses of the 33 kV feeder of the network showed that yearly failure rate, MTTR,MTTF, MTBF, unavailability, availability, SAIFI, SAIDI, ASAI and ASUI were 4.32%, 6.520 h, 23.148 h, 29.668h, 21.98%, 78.02%, 0.0358 interruptions/customer/yr, 0.2336 h/customer/yr, 78.03%, and 21.97%, respectively.These results revealed that the performance indices of the 33 kV feeder with annual total outage frequency (SAIFI)and percentage availability (ASAI) were a far cry from the recommended values of the internationally acceptablestandard value (IASV) of 0.01 and 99.99% respectively. This poses a threat to the reliability and availability ofelectricity supply to consumers.
Ugbowo 2 × 15mva 33/11 kV注压变电站33kv馈线脱扣分析
研究了Ugbowo 2 × 15 MVA 33/11 kV配电网33kv馈线的脱扣剖面。整理并收集了Ugbowo注入变电站2019年9月至2020年8月33 kV馈线日跳闸的年度数据。利用33kv馈线的日停运情况计算Ugbowoinjection变电站的子输电线路(33kv馈线)的月跳闸和年跳闸曲线。使用负载点指数(LPI)分析了12个月(12个月)的月度和年度故障率、MTTR、MTTF、MTBF、可用性、不可用性、SAIFI、SAIDI、ASAI、ASUI等数据,并使用Microsoft Excel图形化地解释了33 kV馈线跳线剖面的结果。对33 kV馈线的年故障率、MTTR、MTTF、MTBF、不可用率、可用性、SAIFI、SAIDI、ASAI和ASUI分别为4.32%、6.520 h、23.148 h、29.668h、21.98%、78.02%、0.0358次中断/客户/年、0.2336 h/客户/年、78.03%和21.97%。结果表明,33 kV馈线的年总停运频率(SAIFI)和可用性百分比(ASAI)的性能指标分别与国际可接受标准值(IASV)的推荐值0.01和99.99%相差甚远。这对消费者电力供应的可靠性和可用性构成了威胁。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信