Thermal properties of natural ester and low viscosity natural ester in the aspect of the reliable operation of the transformer cooling system

G. Dombek, Z. Nadolny, A. Marcinkowska
{"title":"Thermal properties of natural ester and low viscosity natural ester in the aspect of the reliable operation of the transformer cooling system","authors":"G. Dombek, Z. Nadolny, A. Marcinkowska","doi":"10.17531/EIN.2019.3.4","DOIUrl":null,"url":null,"abstract":"The paper presents the results of comparative studies of thermal properties of various types of natural esters used as electroinsulating liquids in transformers. Adequate thermal properties of electro-insulating liquids ensure reliable work of transformers. Two natural esters were selected for the study – one commonly used in distribution transformers, the other characterized by low viscosity. Fourier Transform Infrared Spectroscopy and UV-Visible spectroscopy were used to examine the chemical structure of the examined esters. Properties such as thermal conductivity coefficient λ, kinematic viscosity υ, specific heat cp, density ρ, and thermal expansion coefficient β were analyzed. Heat transfer factor α of the liquid was calculated on the basis of obtained properties. This factor defines the ability of an insulating liquid to heat transport in the transformer, thus determining its reliability. The authors put forward a thesis that a low viscosity natural ester will have a higher heat transfer factor α due to its low viscosity, which affects the factor α. The analysis of thermal properties was carried out for the following temperatures: 25, 40, 60, and 80°C. On the basis of the calculated factor α, the temperature drops in the transformer filled with the analyzed types of natural esters were determined. It has been shown that if a low viscosity natural ester is used in the cooling system of the transformer, the temperature of the hot-spot will be lower. This fact may contribute to more reliable work of transformers and extend its service life.","PeriodicalId":309533,"journal":{"name":"Ekspolatacja i Niezawodnosc - Maintenance and Reliability","volume":"24 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2019-06-20","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"11","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Ekspolatacja i Niezawodnosc - Maintenance and Reliability","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.17531/EIN.2019.3.4","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 11

Abstract

The paper presents the results of comparative studies of thermal properties of various types of natural esters used as electroinsulating liquids in transformers. Adequate thermal properties of electro-insulating liquids ensure reliable work of transformers. Two natural esters were selected for the study – one commonly used in distribution transformers, the other characterized by low viscosity. Fourier Transform Infrared Spectroscopy and UV-Visible spectroscopy were used to examine the chemical structure of the examined esters. Properties such as thermal conductivity coefficient λ, kinematic viscosity υ, specific heat cp, density ρ, and thermal expansion coefficient β were analyzed. Heat transfer factor α of the liquid was calculated on the basis of obtained properties. This factor defines the ability of an insulating liquid to heat transport in the transformer, thus determining its reliability. The authors put forward a thesis that a low viscosity natural ester will have a higher heat transfer factor α due to its low viscosity, which affects the factor α. The analysis of thermal properties was carried out for the following temperatures: 25, 40, 60, and 80°C. On the basis of the calculated factor α, the temperature drops in the transformer filled with the analyzed types of natural esters were determined. It has been shown that if a low viscosity natural ester is used in the cooling system of the transformer, the temperature of the hot-spot will be lower. This fact may contribute to more reliable work of transformers and extend its service life.
天然酯和低粘度天然酯的热性能在变压器冷却系统可靠运行方面的作用
本文介绍了不同类型的天然酯作为变压器电绝缘液的热性能对比研究结果。电绝缘液体具有良好的热性能,确保变压器可靠工作。研究中选择了两种天然酯,一种是配电变压器中常用的酯,另一种是低粘度的酯。利用傅里叶变换红外光谱和紫外可见光谱对所测酯的化学结构进行了表征。分析了导热系数λ、运动粘度υ、比热cp、密度ρ和热膨胀系数β等性能。根据所得性质计算了液体的传热系数α。这一因素决定了绝缘液体在变压器中传热的能力,从而决定了变压器的可靠性。本文提出了低粘度天然酯由于其低粘度而具有较高的换热因子α,从而影响换热因子α。热性能分析在以下温度下进行:25、40、60和80°C。在计算因子α的基础上,确定了所分析的天然酯填充变压器的温降。研究表明,在变压器冷却系统中使用低粘度的天然酯,可以降低热点温度。这有助于提高变压器的工作可靠性,延长变压器的使用寿命。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信