Seul-Ki Kim, Hwachang Song, Byongjun Lee, Sae-Hyuk Kwon
{"title":"Enhancement of Interface Flow Limit using Static Synchronous Series Compensators","authors":"Seul-Ki Kim, Hwachang Song, Byongjun Lee, Sae-Hyuk Kwon","doi":"10.1109/TDC.2006.1668584","DOIUrl":null,"url":null,"abstract":"This paper addresses improving the voltage stability limit of interface flow between two different regions in electric power system using static synchronous series compensators (SSSC). The paper presents a power flow analysis model of SSSC, which is obtained from the injection model of a series voltage source inverter by adding the condition that the SSSC injection voltage is in quadrature with the current of SSSC-installed transmission line. This model is implemented into the modified continuation power flow (MCPF) to investigate the effect of SSSCs on the interface flow. A methodology for determining the interface flow margin is simply briefed. In case study, a 771-bus real system is used to verify that SSSCs enhance the voltage stability limit of interface flow","PeriodicalId":123024,"journal":{"name":"2005/2006 IEEE/PES Transmission and Distribution Conference and Exhibition","volume":"113 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2006-05-21","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"4","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2005/2006 IEEE/PES Transmission and Distribution Conference and Exhibition","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/TDC.2006.1668584","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 4
Abstract
This paper addresses improving the voltage stability limit of interface flow between two different regions in electric power system using static synchronous series compensators (SSSC). The paper presents a power flow analysis model of SSSC, which is obtained from the injection model of a series voltage source inverter by adding the condition that the SSSC injection voltage is in quadrature with the current of SSSC-installed transmission line. This model is implemented into the modified continuation power flow (MCPF) to investigate the effect of SSSCs on the interface flow. A methodology for determining the interface flow margin is simply briefed. In case study, a 771-bus real system is used to verify that SSSCs enhance the voltage stability limit of interface flow