{"title":"Multiple prestriking phenomenon in high voltage transmission substations: Modeling and simulation","authors":"S. Adhikari, D. Mueller, B. Zavadil, C. Pallem, T. Grebe, K. Little","doi":"10.1109/PESGM.2016.7741797","DOIUrl":null,"url":null,"abstract":"This paper presents the prestriking and re-striking phenomenon caused by switching disconnect switches in a high-voltage switchyard. A detailed transient model of a representative utility 345 kV substation was developed in the electromagnetic transient program, EMTP-RV and the phenomenon was studied for different cases of multiple prestrike transients. It was determined that the transient voltages during prestriking could have large differential values which could put much more switching stress on the nearby circuit breaker and other equipment. This could be the probable cause of equipment failure in the future.","PeriodicalId":155315,"journal":{"name":"2016 IEEE Power and Energy Society General Meeting (PESGM)","volume":"66 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2016-07-17","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2016 IEEE Power and Energy Society General Meeting (PESGM)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PESGM.2016.7741797","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
Abstract
This paper presents the prestriking and re-striking phenomenon caused by switching disconnect switches in a high-voltage switchyard. A detailed transient model of a representative utility 345 kV substation was developed in the electromagnetic transient program, EMTP-RV and the phenomenon was studied for different cases of multiple prestrike transients. It was determined that the transient voltages during prestriking could have large differential values which could put much more switching stress on the nearby circuit breaker and other equipment. This could be the probable cause of equipment failure in the future.