Stray neutral current problems and analysis associated with multiple ATS generator installations

S. D. Dunn, F. Wells
{"title":"Stray neutral current problems and analysis associated with multiple ATS generator installations","authors":"S. D. Dunn, F. Wells","doi":"10.1109/ICPS.1998.692552","DOIUrl":null,"url":null,"abstract":"In generator installations where you have more than one 3-pole automatic-transfer-switch (ATS) on a 4-wire system, stray neutral currents and unwanted magnetic fields may arise. These stray currents and fields can cause a multitude of problems. Magnetic fields created by stray neutral currents can cause objectionable current on the conduit system. Objectionable current of this type can cause voltage rises on the grounding system. Geometries of stray neutral current paths can cause magnetic fields through areas of buildings that may cause problems with sensitive electronic equipment. Ground fault protection devices may detect incorrect ground fault condition. The presence of stray ground currents in multi-ATS installations is dependent on equipment selection and bonding connection points, whereas the magnitude of these currents depend on the system geometry, raceway size/types, and other factors. This paper looks at several stray neutral configurations tested in the Vanderbilt Power Laboratory.","PeriodicalId":436140,"journal":{"name":"1998 IEEE Industrial and Commercial Power Systems Technical Conference. Conference Record. Papers Presented at the 1998 Annual Meeting (Cat. No.98CH36202)","volume":"21 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1998-05-03","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"1998 IEEE Industrial and Commercial Power Systems Technical Conference. Conference Record. Papers Presented at the 1998 Annual Meeting (Cat. No.98CH36202)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICPS.1998.692552","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

Abstract

In generator installations where you have more than one 3-pole automatic-transfer-switch (ATS) on a 4-wire system, stray neutral currents and unwanted magnetic fields may arise. These stray currents and fields can cause a multitude of problems. Magnetic fields created by stray neutral currents can cause objectionable current on the conduit system. Objectionable current of this type can cause voltage rises on the grounding system. Geometries of stray neutral current paths can cause magnetic fields through areas of buildings that may cause problems with sensitive electronic equipment. Ground fault protection devices may detect incorrect ground fault condition. The presence of stray ground currents in multi-ATS installations is dependent on equipment selection and bonding connection points, whereas the magnitude of these currents depend on the system geometry, raceway size/types, and other factors. This paper looks at several stray neutral configurations tested in the Vanderbilt Power Laboratory.
与多台ATS发电机安装相关的杂散中性电流问题及分析
在4线制系统上安装多个3极自动转换开关(ATS)的发电机装置中,可能会产生杂散的中性电流和不必要的磁场。这些杂散的电流和场会引起许多问题。由杂散中性电流产生的磁场会对导管系统产生不良电流。这种类型的不良电流会引起接地系统的电压升高。杂散中性电流路径的几何形状可能会在建筑物区域产生磁场,从而可能导致敏感电子设备出现问题。接地故障保护装置可以检测到不正确的接地故障情况。在多ats安装中,杂散接地电流的存在取决于设备选择和bonding连接点,而这些电流的大小取决于系统几何形状、滚道尺寸/类型和其他因素。本文着眼于在范德比尔特电力实验室测试的几种杂散中性配置。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信