{"title":"Research on Short-time Current Test Method of DC Circuit Breaker Used in DC Grid","authors":"Xiuhuan Wang, Junchuan Zhou, E. Chen","doi":"10.1109/POWERCON53785.2021.9697544","DOIUrl":null,"url":null,"abstract":"DC power grid technology puts forward new requirements for equipment. High-voltage DC circuit breakers with fast breaking capability are the core equipment of DC power grids. The existing test technology can not meet the short-term current tolerance requirements of DC circuit breakers in terms of power. In order to solve this problem, this paper analyzes the short-term current stress tolerated by the DC circuit breaker in the DC grid, proposes a test method and test circuit topology based on the loss and junction temperature equivalence are proposed, and builds a PSCAD/EMTDC electromagnetic transient simulation model. Taking the Kangbao Station of Zhangbei Project as an example, the short-term current withstand test of the DC circuit breaker was simulated and verified. The simulation results show that the test circuit can effectively implement the short-term current stress assessment of the DC circuit breaker. The design provides guidance for the test platform.","PeriodicalId":216155,"journal":{"name":"2021 International Conference on Power System Technology (POWERCON)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2021-12-08","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2021 International Conference on Power System Technology (POWERCON)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/POWERCON53785.2021.9697544","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
Abstract
DC power grid technology puts forward new requirements for equipment. High-voltage DC circuit breakers with fast breaking capability are the core equipment of DC power grids. The existing test technology can not meet the short-term current tolerance requirements of DC circuit breakers in terms of power. In order to solve this problem, this paper analyzes the short-term current stress tolerated by the DC circuit breaker in the DC grid, proposes a test method and test circuit topology based on the loss and junction temperature equivalence are proposed, and builds a PSCAD/EMTDC electromagnetic transient simulation model. Taking the Kangbao Station of Zhangbei Project as an example, the short-term current withstand test of the DC circuit breaker was simulated and verified. The simulation results show that the test circuit can effectively implement the short-term current stress assessment of the DC circuit breaker. The design provides guidance for the test platform.