R. Muñoz-Aguilar, P. Rodríguez, A. Dòria-Cerezo, I. Candela, A. Luna
{"title":"Sensor-less Sliding Mode Control of a stand-alone wound rotor synchronous generator with unbalanced load","authors":"R. Muñoz-Aguilar, P. Rodríguez, A. Dòria-Cerezo, I. Candela, A. Luna","doi":"10.1109/IECON.2011.6119960","DOIUrl":null,"url":null,"abstract":"This paper presents a Sliding Mode Control for a wound rotor synchronous machine acting as an isolated generator connected to an unbalanced load. In order to simplify the control methodology, the standard dq-model of the machine is connected to a balanced resistive load. A switching function is defined in order to fulfill the control objective. From the desired surface, the standard sliding methodology is applied to obtain a robust and very simple controller. Then, the actual measured voltage of the machines is acquired and treated trough a frequency locked loop algorithm in order to extract the positive sequence and control it to guarantee a good definition of the park transformation. A phase locked loop algorithm is also used to avoid speed sensors. Numerical simulations a validate the control law and show good performance and a fast response to load and reference changes.","PeriodicalId":105539,"journal":{"name":"IECON 2011 - 37th Annual Conference of the IEEE Industrial Electronics Society","volume":"38 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2011-11-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"3","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"IECON 2011 - 37th Annual Conference of the IEEE Industrial Electronics Society","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/IECON.2011.6119960","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 3
Abstract
This paper presents a Sliding Mode Control for a wound rotor synchronous machine acting as an isolated generator connected to an unbalanced load. In order to simplify the control methodology, the standard dq-model of the machine is connected to a balanced resistive load. A switching function is defined in order to fulfill the control objective. From the desired surface, the standard sliding methodology is applied to obtain a robust and very simple controller. Then, the actual measured voltage of the machines is acquired and treated trough a frequency locked loop algorithm in order to extract the positive sequence and control it to guarantee a good definition of the park transformation. A phase locked loop algorithm is also used to avoid speed sensors. Numerical simulations a validate the control law and show good performance and a fast response to load and reference changes.