{"title":"Harmonic current emission of photovoltaic installations under system conditions","authors":"Juergen Schlabbach","doi":"10.1109/EEM.2008.4579000","DOIUrl":null,"url":null,"abstract":"Harmonic currents of PV-inverters show a significant dependency on the harmonic voltage content of the AC-system voltage. Measurements of harmonic currents were carried out in LV-systems and under laboratory test conditions with adjustable harmonic content of the AV-voltage. Two PV-inverters, one with coupling transformer and one without transformer were tested. The results indicated that the emitted harmonic currents depend strongly on the harmonic voltages prevailing in the AC-voltage. PV-inverters without transformer show significant lower harmonic currents than inverters with coupling transformer. The standard test conditions as defined in international standards does not consider real system conditions with respect to the harmonic voltages in system voltage. The measured currents as documented in data sheets are therefore comparatively lower than under the condition of real system operation.","PeriodicalId":118618,"journal":{"name":"2008 5th International Conference on the European Electricity Market","volume":"9 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2008-05-28","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"26","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2008 5th International Conference on the European Electricity Market","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/EEM.2008.4579000","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 26
Abstract
Harmonic currents of PV-inverters show a significant dependency on the harmonic voltage content of the AC-system voltage. Measurements of harmonic currents were carried out in LV-systems and under laboratory test conditions with adjustable harmonic content of the AV-voltage. Two PV-inverters, one with coupling transformer and one without transformer were tested. The results indicated that the emitted harmonic currents depend strongly on the harmonic voltages prevailing in the AC-voltage. PV-inverters without transformer show significant lower harmonic currents than inverters with coupling transformer. The standard test conditions as defined in international standards does not consider real system conditions with respect to the harmonic voltages in system voltage. The measured currents as documented in data sheets are therefore comparatively lower than under the condition of real system operation.