Differential lightning protection research on ± 800kv UHVDC transmission lines

L. Zhang, Y. Li, W. Shi, Y. Yin, M. Dai, P. Kang, T. Lei
{"title":"Differential lightning protection research on ± 800kv UHVDC transmission lines","authors":"L. Zhang, Y. Li, W. Shi, Y. Yin, M. Dai, P. Kang, T. Lei","doi":"10.1049/icp.2021.2562","DOIUrl":null,"url":null,"abstract":"This paper carried out the further research on differential lightning protection of UHVDC transmission lines, which was based on the ±800kV UHVDC project from Qinghai to Henan. According to the design parameters at the construction stage, the lightning protection performance of the project was studied, and the backflashover rate and the shielding failure flashover rate were given in this paper. By comparing the calculation results of this project and the projects already built, the rationality of the simulation calculation results was verified. In this paper, the mountainous terrain is classified, and the principle of electrical geometric model (EGM model) is used to research the shielding failure flashover rate deeply under different mountainous terrain. Because the whole transmission line of the project was located in the thunderstorm area, the vulnerable section was proposed based on the ground inclination angle, and the lightning protection differentiation measures were proposed for the vulnerable section. After the lightning optimization measures were adopted, the lightning flashover rate of transmission line from Qinghai to Henan was almostly reduced to 0.1 times/100km in 40 thunderstorm day area, which meet the requirements of the standard named as “guide for lightning protection of overhead transmission lines”. The results obtained in this paper can be used as the reference for engineering design.","PeriodicalId":242596,"journal":{"name":"2021 Annual Meeting of CSEE Study Committee of HVDC and Power Electronics (HVDC 2021)","volume":"112 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1900-01-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2021 Annual Meeting of CSEE Study Committee of HVDC and Power Electronics (HVDC 2021)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1049/icp.2021.2562","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

This paper carried out the further research on differential lightning protection of UHVDC transmission lines, which was based on the ±800kV UHVDC project from Qinghai to Henan. According to the design parameters at the construction stage, the lightning protection performance of the project was studied, and the backflashover rate and the shielding failure flashover rate were given in this paper. By comparing the calculation results of this project and the projects already built, the rationality of the simulation calculation results was verified. In this paper, the mountainous terrain is classified, and the principle of electrical geometric model (EGM model) is used to research the shielding failure flashover rate deeply under different mountainous terrain. Because the whole transmission line of the project was located in the thunderstorm area, the vulnerable section was proposed based on the ground inclination angle, and the lightning protection differentiation measures were proposed for the vulnerable section. After the lightning optimization measures were adopted, the lightning flashover rate of transmission line from Qinghai to Henan was almostly reduced to 0.1 times/100km in 40 thunderstorm day area, which meet the requirements of the standard named as “guide for lightning protection of overhead transmission lines”. The results obtained in this paper can be used as the reference for engineering design.
±800kv特高压直流输电线路差动防雷研究
本文以青海至河南±800kV特高压直流工程为例,对特高压直流输电线路差动防雷进行了进一步的研究。根据施工阶段的设计参数,对工程的防雷性能进行了研究,给出了反闪络率和屏蔽失效闪络率。通过与已建工程的计算结果对比,验证了仿真计算结果的合理性。本文对山地地形进行了分类,利用电几何模型(EGM)原理,深入研究了不同山地地形下屏蔽失效闪络率。由于本工程整个输电线路位于雷暴地区,根据地面倾角提出了易损段,并对易损段提出了防雷分异措施。采取雷电优化措施后,40雷雨天区域青海至河南输电线路雷电闪络率基本降至0.1次/100km,满足《架空输电线路防雷导则》标准要求。所得结果可作为工程设计的参考。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信