Parallel redundant operation of UPS with robust current minor loop

Y. Ito, O. Iyama
{"title":"Parallel redundant operation of UPS with robust current minor loop","authors":"Y. Ito, O. Iyama","doi":"10.1109/PCCON.1997.645660","DOIUrl":null,"url":null,"abstract":"This paper describes a control method of UPS inverters connected in parallel. The UPS output voltage is controlled by an algorithm with an inverter current. A minor loop using two types of observers. Only the following two points are added to the algorithm for realizing parallel operations: (1) feedback of a common load current instead of the UPS output current; and (2) adjusting the phase of the output voltage to make the reactive component of the circulating currents zero. The proposed method has the following features, compared with conventional methods; (1) it does not need an additional output voltage control for parallel operation; (2) the impedances among UPSs are resistive so that the circulating currents caused by phase difference among UPSs have only reactive components; and (3) increase of software for parallel operation control is minimal.","PeriodicalId":262154,"journal":{"name":"Proceedings of Power Conversion Conference - PCC '97","volume":"32 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1997-08-03","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"31","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Proceedings of Power Conversion Conference - PCC '97","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PCCON.1997.645660","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 31

Abstract

This paper describes a control method of UPS inverters connected in parallel. The UPS output voltage is controlled by an algorithm with an inverter current. A minor loop using two types of observers. Only the following two points are added to the algorithm for realizing parallel operations: (1) feedback of a common load current instead of the UPS output current; and (2) adjusting the phase of the output voltage to make the reactive component of the circulating currents zero. The proposed method has the following features, compared with conventional methods; (1) it does not need an additional output voltage control for parallel operation; (2) the impedances among UPSs are resistive so that the circulating currents caused by phase difference among UPSs have only reactive components; and (3) increase of software for parallel operation control is minimal.
具有稳健电流小回路的UPS并联冗余运行
本文介绍了一种UPS逆变器并联控制方法。UPS的输出电压由一种带有逆变器电流的算法控制。使用两种类型的观察器的小循环。为实现并行运算,算法只增加了以下两点:(1)用公共负载电流反馈,而不是UPS输出电流;(2)调整输出电压的相位,使循环电流的无功分量为零。与传统方法相比,该方法具有以下特点:(1)并联运行时不需要额外的输出电压控制;(2) ups之间的阻抗是电阻性的,因此ups之间相位差引起的循环电流只有无功分量;(3)并行运行控制软件的增加很少。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信