A Case Analysis on Intermittent Multi-point Grounding of Transformer Core Based on Dissolved Gas Analysis and Partial Discharge Location

Zhou Bo, Gao Jun, Yang Hongquan, Liu Yanqing, L. Xing, Qiu Wei, Yang Xinchun, Guo Chao
{"title":"A Case Analysis on Intermittent Multi-point Grounding of Transformer Core Based on Dissolved Gas Analysis and Partial Discharge Location","authors":"Zhou Bo, Gao Jun, Yang Hongquan, Liu Yanqing, L. Xing, Qiu Wei, Yang Xinchun, Guo Chao","doi":"10.1109/ICHVE53725.2022.9961622","DOIUrl":null,"url":null,"abstract":"Aiming at the problem that the content of acetylene and total hydrocarbons in the insulating oil exceeds the standard during the operation of a 110kV transformer, a bisection plane positioning method based on the UHF is used to accurately locate the partial discharge position. Secondly, the intermittent multi-point ground fault of the transformer core was found through the the windlass cover of the transformer, which successfully verified the accuracy of PD positioning. Finally, the reasons and process of discharge are discussed in depth.","PeriodicalId":125983,"journal":{"name":"2022 IEEE International Conference on High Voltage Engineering and Applications (ICHVE)","volume":"207 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2022-09-25","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2022 IEEE International Conference on High Voltage Engineering and Applications (ICHVE)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICHVE53725.2022.9961622","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

Aiming at the problem that the content of acetylene and total hydrocarbons in the insulating oil exceeds the standard during the operation of a 110kV transformer, a bisection plane positioning method based on the UHF is used to accurately locate the partial discharge position. Secondly, the intermittent multi-point ground fault of the transformer core was found through the the windlass cover of the transformer, which successfully verified the accuracy of PD positioning. Finally, the reasons and process of discharge are discussed in depth.
基于溶解气体分析和局部放电定位的变压器铁心间歇多点接地实例分析
针对110kV变压器运行过程中绝缘油中乙炔和总烃含量超标的问题,采用基于超高频的二分面定位方法对局部放电位置进行了精确定位。其次,通过变压器绞车罩发现变压器铁心的间歇性多点接地故障,成功验证了PD定位的准确性。最后,对放电的原因和过程进行了深入的探讨。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信