W. Brumsickle, G. Luckjiff, R. Schneider, D. Divan, M. McGranaghan
{"title":"Dynamic sag correctors: cost effective industrial power line conditioning","authors":"W. Brumsickle, G. Luckjiff, R. Schneider, D. Divan, M. McGranaghan","doi":"10.1109/IAS.1999.801675","DOIUrl":null,"url":null,"abstract":"Voltage sags, transients, and momentary interruption of power together constitute 92% of the PQ problems encountered by typical industrial customers. The series-parallel connected dynamic sag corrector (DySC) provides statistically significant protection at greatly reduced cost. The DySC is rated 1.5 kVA 1-phase to 2000 kVA 3-phase and features a patented single stage power conversion circuit with minimal stored energy. A unique circuit allows operation with opened upstream circuit breaker. The paper presents a detailed discussion of DySC operating principles and validation of performance. It also provides conditions under which this new category of product can be applied.","PeriodicalId":125787,"journal":{"name":"Conference Record of the 1999 IEEE Industry Applications Conference. Thirty-Forth IAS Annual Meeting (Cat. No.99CH36370)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1999-10-03","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"251","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Conference Record of the 1999 IEEE Industry Applications Conference. Thirty-Forth IAS Annual Meeting (Cat. No.99CH36370)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/IAS.1999.801675","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 251
Abstract
Voltage sags, transients, and momentary interruption of power together constitute 92% of the PQ problems encountered by typical industrial customers. The series-parallel connected dynamic sag corrector (DySC) provides statistically significant protection at greatly reduced cost. The DySC is rated 1.5 kVA 1-phase to 2000 kVA 3-phase and features a patented single stage power conversion circuit with minimal stored energy. A unique circuit allows operation with opened upstream circuit breaker. The paper presents a detailed discussion of DySC operating principles and validation of performance. It also provides conditions under which this new category of product can be applied.