The Test of Leakage Current of Terminal Stator Winding of the 4# Generator and Defects Treatment

Kunpeng Tian, Ping Li, Yu Zhao, Xingwei Fei
{"title":"The Test of Leakage Current of Terminal Stator Winding of the 4# Generator and Defects Treatment","authors":"Kunpeng Tian, Ping Li, Yu Zhao, Xingwei Fei","doi":"10.1115/icone29-93102","DOIUrl":null,"url":null,"abstract":"\n The insulation status of generator stator winding is related to the safe and stable operation of generator. When we repair the generator, we need different testing methods to verify the insulation of the different positions of the generator stator winding. In recent years, there is many short-circuit faults because of the insulation defect on the terminal of the stator winding. In generally, when generator need to be repaired, we do the AC/DC withstand voltage test. But when the results of AC/DC withstand voltage test are both OK, the insulation of the stator terminal winding is still not OK. that is the proof that the AC/DC withstand voltage test is not all-powerful. The test of leakage current of terminal stator winding is good effective method to checkout the the insulation of the stator terminal winding. We can find the insulation defect on the terminal of the stator winding with this test and avoid affecting the production even equipment damage.","PeriodicalId":110070,"journal":{"name":"Volume 1: Nuclear Plant Operation and Maintenance, Engineering and Modification, Operation Life Extension (OLE), and Life Cycle","volume":"98 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2022-08-08","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Volume 1: Nuclear Plant Operation and Maintenance, Engineering and Modification, Operation Life Extension (OLE), and Life Cycle","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1115/icone29-93102","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

The insulation status of generator stator winding is related to the safe and stable operation of generator. When we repair the generator, we need different testing methods to verify the insulation of the different positions of the generator stator winding. In recent years, there is many short-circuit faults because of the insulation defect on the terminal of the stator winding. In generally, when generator need to be repaired, we do the AC/DC withstand voltage test. But when the results of AC/DC withstand voltage test are both OK, the insulation of the stator terminal winding is still not OK. that is the proof that the AC/DC withstand voltage test is not all-powerful. The test of leakage current of terminal stator winding is good effective method to checkout the the insulation of the stator terminal winding. We can find the insulation defect on the terminal of the stator winding with this test and avoid affecting the production even equipment damage.
4#发电机定子终端绕组漏电流测试及缺陷处理
发电机定子绕组的绝缘状况关系到发电机的安全稳定运行。我们在检修发电机时,需要用不同的测试方法来验证发电机定子绕组不同位置的绝缘情况。近年来,由于定子绕组端部的绝缘缺陷引起的短路故障较多。在一般情况下,当发电机需要检修时,我们会进行交/直流耐压试验。但当交/直流耐压试验结果均OK时,定子端子绕组的绝缘仍不OK。这证明了AC/DC耐压测试并不是万能的。定子终端绕组漏电流测试是检测定子终端绕组绝缘性的一种有效方法。通过此试验可以发现定子绕组端子处的绝缘缺陷,避免影响生产甚至设备损坏。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信
小红书