Evaluation of sympathetic nuisance tripping involving instantaneous ground fault relays and general considerations for ground fault protection of industrial power systems

D. Ventruella
{"title":"Evaluation of sympathetic nuisance tripping involving instantaneous ground fault relays and general considerations for ground fault protection of industrial power systems","authors":"D. Ventruella","doi":"10.1109/PAPCON.1998.685498","DOIUrl":null,"url":null,"abstract":"The behavior of ground fault relays in large industrial power systems is generally perceived to be well-understood. In reality, the behavior of these relays can be influenced by more than the magnitude of 60 Hz ground fault induced short circuit currents, current transformer ratios, and relay tap settings. This paper addresses issues that can lead to sympathetic nuisance tripping of ground fault relays and other ground fault protection concerns. Sympathetic nuisance tripping occurs if a feeder with no conventional ground fault current source (generator or utility tie transformer) downstream from the feeder circuit breaker trips when a ground fault occurs elsewhere on the power system. The advantages and disadvantages of various types of ground fault sensing relay configurations are also discussed. Specific protection application considerations relating to high resistance grounding are presented.","PeriodicalId":360061,"journal":{"name":"Conference Record of 1998 Annual Pulp and Paper Industry Technical Conference (Cat. No.98CH36219)","volume":"352 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"1998-06-21","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Conference Record of 1998 Annual Pulp and Paper Industry Technical Conference (Cat. No.98CH36219)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PAPCON.1998.685498","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2

Abstract

The behavior of ground fault relays in large industrial power systems is generally perceived to be well-understood. In reality, the behavior of these relays can be influenced by more than the magnitude of 60 Hz ground fault induced short circuit currents, current transformer ratios, and relay tap settings. This paper addresses issues that can lead to sympathetic nuisance tripping of ground fault relays and other ground fault protection concerns. Sympathetic nuisance tripping occurs if a feeder with no conventional ground fault current source (generator or utility tie transformer) downstream from the feeder circuit breaker trips when a ground fault occurs elsewhere on the power system. The advantages and disadvantages of various types of ground fault sensing relay configurations are also discussed. Specific protection application considerations relating to high resistance grounding are presented.
涉及瞬时接地故障继电器的交感有害跳闸的评估和工业电力系统接地故障保护的一般考虑
在大型工业电力系统中,接地故障继电器的行为通常被认为是很容易理解的。实际上,这些继电器的行为可能受到超过60hz接地故障引起的短路电流、电流互感器比率和继电器分接设置的影响。本文解决了可能导致接地故障继电器的交感干扰跳闸和其他接地故障保护问题。当电力系统的其他地方发生接地故障时,如果从馈线断路器下游没有常规接地故障电流源(发电机或公用变压器)的馈线跳闸,则会发生交感滋扰跳闸。讨论了各种接地故障感应继电器配置的优缺点。介绍了与高阻接地有关的具体保护应用注意事项。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信