Modified discrete Fourier transform algorithm for protection of shunt compensated distribution line

A. Jani, V. Makwana
{"title":"Modified discrete Fourier transform algorithm for protection of shunt compensated distribution line","authors":"A. Jani, V. Makwana","doi":"10.20998/2074-272x.2023.2.10","DOIUrl":null,"url":null,"abstract":"Introduction. The response time of the relay plays vital role when fault occurs on the line. Various algorithms are adopted to increase the sampling rate of the relay which, in turn, improves the response time. Methods. Discrete Fourier transform and modified discrete Fourier transform are the two algorithms used to calculate the fundamental frequency phasor of the signal required by the relay to initiate trip command. It is known that discrete Fourier transform takes four to five cycles to produce the fundamental frequency phasor but it fails to deal with the decaying DC component. On the other hand, modified discrete Fourier transform improves the response time by removing the decaying DC component along with the other harmonics in just one cycle and a few samples. The aim of this paper is to cover discrete Fourier transform and modified discrete Fourier transform algorithms to analyze the performance of the three overcurrent and one earth fault relaying scheme for different types of faults occurring in the distribution system. Methodology. The concept of three overcurrent and one earth fault scheme is also explained in this paper for protection of shunt-compensated distribution system. The scheme is designed for variable power factor. MATLAB/Simulink is used as the software tool to validate the results obtained for various types of faults occurring in the system. The results are represented graphically to illustrate the time of response of the protection scheme when shunt compensators are connected at the receiving end of distribution network.","PeriodicalId":170736,"journal":{"name":"Electrical Engineering & Electromechanics","volume":"55 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2023-03-05","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Electrical Engineering & Electromechanics","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.20998/2074-272x.2023.2.10","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

Introduction. The response time of the relay plays vital role when fault occurs on the line. Various algorithms are adopted to increase the sampling rate of the relay which, in turn, improves the response time. Methods. Discrete Fourier transform and modified discrete Fourier transform are the two algorithms used to calculate the fundamental frequency phasor of the signal required by the relay to initiate trip command. It is known that discrete Fourier transform takes four to five cycles to produce the fundamental frequency phasor but it fails to deal with the decaying DC component. On the other hand, modified discrete Fourier transform improves the response time by removing the decaying DC component along with the other harmonics in just one cycle and a few samples. The aim of this paper is to cover discrete Fourier transform and modified discrete Fourier transform algorithms to analyze the performance of the three overcurrent and one earth fault relaying scheme for different types of faults occurring in the distribution system. Methodology. The concept of three overcurrent and one earth fault scheme is also explained in this paper for protection of shunt-compensated distribution system. The scheme is designed for variable power factor. MATLAB/Simulink is used as the software tool to validate the results obtained for various types of faults occurring in the system. The results are represented graphically to illustrate the time of response of the protection scheme when shunt compensators are connected at the receiving end of distribution network.
并联补偿配电线路保护的改进离散傅里叶变换算法
介绍。当线路发生故障时,继电器的响应时间起着至关重要的作用。采用各种算法来提高继电器的采样率,从而提高响应时间。方法。离散傅里叶变换和改进离散傅里叶变换是用于计算继电器启动跳闸命令所需信号的基频相量的两种算法。众所周知,离散傅里叶变换需要4到5个周期才能产生基频相量,但它无法处理衰减的直流分量。另一方面,改进的离散傅里叶变换通过在一个周期和几个样本中去除衰减的直流分量以及其他谐波来改善响应时间。本文的目的是利用离散傅立叶变换和改进的离散傅立叶变换算法来分析配电系统中发生的不同类型故障时三过流一接地故障继电保护方案的性能。方法。本文还阐述了并联补偿配电系统保护的三过流一接地方案的概念。该方案是针对可变功率因数设计的。针对系统中出现的各种类型的故障,采用MATLAB/Simulink作为软件工具对得到的结果进行验证。用图形表示了配电网接收端接并联补偿器时保护方案的响应时间。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信