Electrical load flow analysis of Auchi distribution network without load shedding

Micheal Rotimi Adu, Isah Osilama Oshiobugie, Tolulope David Makanju
{"title":"Electrical load flow analysis of Auchi distribution network without load shedding","authors":"Micheal Rotimi Adu, Isah Osilama Oshiobugie, Tolulope David Makanju","doi":"10.53430/ijeru.2023.4.2.0020","DOIUrl":null,"url":null,"abstract":"The occurrence of loadshedding under normal operating condition in Distribution Network caused a lot of inconveniences to the consumer. However, there is need to examine the state of the distribution network to know the performance without load shedding under normal condition. This research examines the state of Auchi distribution network without load shedding. In order to achieve the aim of the research data was obtained from the distribution company, the modelling of the distribution network obtained was done using ETAP and the load flow simulation was done using Newton Raphson Algorithm to determine the power flow in the network, Bus voltage, losses along the line and transformer losses. The results of the study show that at 80% loading of the transformers in the network, the voltage supply to the consumer is bad under normal condition, since the two out of three 33 kV bus voltages is below the acceptable range of plus or minus 5% of the nominal voltage. Likewise, almost all 11 kV and 0.415kV voltages in the network is below the acceptable limit of plus or minus 10% of the nominal voltage. Furthermore, the result indicates that active power loss in the network is 0.2MW which is very high. This research therefore recommends that the voltage profile of AUCHI distribution network needs improvement in order to improve the quality of supply. Also, since the supply from the grid is be allocated based on the generating capacity this research also recommends that DISCO in charge of Auchi distribution network should also considering the usage of DG in the network which can perform a dual purpose of voltage improvement and addition of power supplied.","PeriodicalId":423246,"journal":{"name":"International Journal of Engineering Research Updates","volume":"68 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2023-05-30","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"International Journal of Engineering Research Updates","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.53430/ijeru.2023.4.2.0020","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

The occurrence of loadshedding under normal operating condition in Distribution Network caused a lot of inconveniences to the consumer. However, there is need to examine the state of the distribution network to know the performance without load shedding under normal condition. This research examines the state of Auchi distribution network without load shedding. In order to achieve the aim of the research data was obtained from the distribution company, the modelling of the distribution network obtained was done using ETAP and the load flow simulation was done using Newton Raphson Algorithm to determine the power flow in the network, Bus voltage, losses along the line and transformer losses. The results of the study show that at 80% loading of the transformers in the network, the voltage supply to the consumer is bad under normal condition, since the two out of three 33 kV bus voltages is below the acceptable range of plus or minus 5% of the nominal voltage. Likewise, almost all 11 kV and 0.415kV voltages in the network is below the acceptable limit of plus or minus 10% of the nominal voltage. Furthermore, the result indicates that active power loss in the network is 0.2MW which is very high. This research therefore recommends that the voltage profile of AUCHI distribution network needs improvement in order to improve the quality of supply. Also, since the supply from the grid is be allocated based on the generating capacity this research also recommends that DISCO in charge of Auchi distribution network should also considering the usage of DG in the network which can perform a dual purpose of voltage improvement and addition of power supplied.
无减载的Auchi配电网负荷潮流分析
配电网在正常运行情况下出现的减载现象给用户带来了诸多不便。但是,要了解配电网在正常情况下无减载的性能,需要对配电网的状态进行检查。本研究考察无减载的Auchi配电网状态。为了达到研究目的,从配电网公司获取数据,利用ETAP对得到的配电网进行建模,并利用Newton Raphson算法对配电网进行潮流仿真,确定电网中的潮流、母线电压、沿途损耗和变压器损耗。研究结果表明,在电网中变压器负荷为80%时,正常情况下向用户供电的电压较差,因为三分之二的33千伏母线电压低于标称电压正负5%的可接受范围。同样,网络中几乎所有的11kv和0.415kV电压都低于标称电压正负10%的可接受限值。结果表明,电网有功功率损耗高达0.2MW。因此,本研究建议对AUCHI配电网的电压分布进行改进,以提高供电质量。此外,由于电网供电是根据发电能力分配的,本研究还建议负责Auchi配电网的DISCO也应考虑DG在网络中的使用,DG可以达到改善电压和增加供电的双重目的。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信