On the specification of requirements for the activation dynamics of Frequency Containment Reserves

Philipp Maucher, H. Lens
{"title":"On the specification of requirements for the activation dynamics of Frequency Containment Reserves","authors":"Philipp Maucher, H. Lens","doi":"10.1109/SmartGridComm51999.2021.9632295","DOIUrl":null,"url":null,"abstract":"The dynamic requirements for the provision of Frequency Containment Reserves (FCR) in Continental Europe are defined in the respective network codes (e.g. System Operation Guideline). However, this definition is precise only for a sudden frequency deviation of ±200 mHz. The requirements for smaller and/or slower frequency deviations are only described indirectly by referring to the case of ±200 mHz. As a result, different interpretations are possible, among which requiring activation dynamics that a) correspond to a linear time-invariant (LTI) system or b) exhibit a constant rate of change of power (RoCoP). This paper assesses the effects of these two different requirement interpretations on FCR providers and system stability by comparing their effect for different frequency deviations. It turns out that the RoCoP interpretation is disadvantageous, as it provides a slower response for large and fast frequency deviations and a fast response for small frequency deviations. Apart from Battery Energy Storage Systems (BESS), most FCR providers cannot perform FCR activation with a fixed RoCoP. In a further step, we consider the effects of the different requirement interpretations on system stability. For a constant RoCoP, it is assumed that the FCR is provided by BESS, while a conventional power plant model is used to implement LTI behavior. The comparison is performed both with model parameters corresponding to the current grid and with model parameters corresponding to a future grid. For each grid model, two scenarios are considered: The first scenario considers active power imbalances caused by load noise only (normal operation), while the second takes an additional significant generation outage into account (contingency). The results show that, in the load noise scenario, FCR activation with constant RoCoP reduces the frequency deviations slightly at the cost of higher total FCR provision and higher maximum FCR activation. However, in case of an additional generation outage, constant RoCoP activation results in a larger maximum frequency deviation, which means that the stability margin of the system is reduced.","PeriodicalId":378884,"journal":{"name":"2021 IEEE International Conference on Communications, Control, and Computing Technologies for Smart Grids (SmartGridComm)","volume":"358 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2021-10-25","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2021 IEEE International Conference on Communications, Control, and Computing Technologies for Smart Grids (SmartGridComm)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/SmartGridComm51999.2021.9632295","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

Abstract

The dynamic requirements for the provision of Frequency Containment Reserves (FCR) in Continental Europe are defined in the respective network codes (e.g. System Operation Guideline). However, this definition is precise only for a sudden frequency deviation of ±200 mHz. The requirements for smaller and/or slower frequency deviations are only described indirectly by referring to the case of ±200 mHz. As a result, different interpretations are possible, among which requiring activation dynamics that a) correspond to a linear time-invariant (LTI) system or b) exhibit a constant rate of change of power (RoCoP). This paper assesses the effects of these two different requirement interpretations on FCR providers and system stability by comparing their effect for different frequency deviations. It turns out that the RoCoP interpretation is disadvantageous, as it provides a slower response for large and fast frequency deviations and a fast response for small frequency deviations. Apart from Battery Energy Storage Systems (BESS), most FCR providers cannot perform FCR activation with a fixed RoCoP. In a further step, we consider the effects of the different requirement interpretations on system stability. For a constant RoCoP, it is assumed that the FCR is provided by BESS, while a conventional power plant model is used to implement LTI behavior. The comparison is performed both with model parameters corresponding to the current grid and with model parameters corresponding to a future grid. For each grid model, two scenarios are considered: The first scenario considers active power imbalances caused by load noise only (normal operation), while the second takes an additional significant generation outage into account (contingency). The results show that, in the load noise scenario, FCR activation with constant RoCoP reduces the frequency deviations slightly at the cost of higher total FCR provision and higher maximum FCR activation. However, in case of an additional generation outage, constant RoCoP activation results in a larger maximum frequency deviation, which means that the stability margin of the system is reduced.
频率控制储备的激活动力学要求规范
在欧洲大陆,提供频率遏制储备(FCR)的动态要求在各自的网络代码(例如系统操作指南)中进行了定义。然而,此定义仅适用于±200mhz的突然频率偏差。对于更小和/或更慢的频率偏差的要求,仅参考±200mhz的情况间接描述。因此,可能有不同的解释,其中需要激活动力学a)对应于线性时不变(LTI)系统或b)表现出恒定的功率变化率(RoCoP)。本文通过比较两种不同的需求解释在不同频率偏差下对FCR提供商和系统稳定性的影响,来评估这两种不同需求解释对FCR提供商和系统稳定性的影响。事实证明,RoCoP解释是不利的,因为它对大而快的频率偏差提供较慢的响应,而对小的频率偏差提供较快的响应。除了电池储能系统(BESS)之外,大多数FCR供应商都无法使用固定的RoCoP进行FCR激活。在进一步的步骤中,我们考虑了不同需求解释对系统稳定性的影响。对于恒定RoCoP,假设FCR由BESS提供,而采用传统电厂模型实现LTI行为。与当前网格对应的模型参数和与未来网格对应的模型参数进行比较。对于每个电网模型,考虑了两种情况:第一种情况只考虑由负载噪声(正常运行)引起的有功功率不平衡,而第二种情况考虑了额外的重大发电中断(应急)。结果表明,在负载噪声情况下,恒定RoCoP的FCR激活可以略微降低频率偏差,但代价是更高的总FCR供应和更高的最大FCR激活。然而,在额外的发电中断情况下,持续激活RoCoP会导致更大的最大频率偏差,这意味着系统的稳定裕度会降低。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信