Study on the interface partial discharge between silicone rubber and fiber reinforced plastic in composite insulators

Bao Weining, Liu Yingyan, Gao Yanfeng, Liu Shaohua, Xidong Liang, Wang Jiafu
{"title":"Study on the interface partial discharge between silicone rubber and fiber reinforced plastic in composite insulators","authors":"Bao Weining, Liu Yingyan, Gao Yanfeng, Liu Shaohua, Xidong Liang, Wang Jiafu","doi":"10.1109/CEIDP.2015.7352042","DOIUrl":null,"url":null,"abstract":"The internal macroscopic interface, which is between fiber reinforced plastic (FRP) and silicone rubber, is the weak point in the whole composite insulation system, in general. Moisture ingress may lead to interfacial adhesion loss and even cause a significant decline of insulation properties. It should be noted that, it is lack of the detection method for interface electrical properties. In this study, an electrode system is designed and manufactured to measure the interface partial discharge (PD). The electrodes are embedded into the interface during the curing process. As we know, when the composite insulators encounter liquids, the liquids may permeate into the silicone rubber housing via diffusion process and reach the interface between the silicone rubber and FRP, which may cause the damage to the interface and also the change of PD properties under ac voltages. In our study, the PD properties in the interface before and after liquids permeation were measured by a PD measurement system. The liquids we chose in this study were three kinds, including deionized water, NaCl solution and HNO3 solution, since composite insulators encountered such kinds of liquids in practice. Since the permeation time for liquids was the key point, different values of PD were gained after several different days' permeation, which may reflect the deterioration process of the interface. Our PD research, together with the past test results about interface resistivity, could provide an in-depth understanding of the interface performance in composite insulators.","PeriodicalId":432404,"journal":{"name":"2015 IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP)","volume":"15 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2015-12-17","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"3","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2015 IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/CEIDP.2015.7352042","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 3

Abstract

The internal macroscopic interface, which is between fiber reinforced plastic (FRP) and silicone rubber, is the weak point in the whole composite insulation system, in general. Moisture ingress may lead to interfacial adhesion loss and even cause a significant decline of insulation properties. It should be noted that, it is lack of the detection method for interface electrical properties. In this study, an electrode system is designed and manufactured to measure the interface partial discharge (PD). The electrodes are embedded into the interface during the curing process. As we know, when the composite insulators encounter liquids, the liquids may permeate into the silicone rubber housing via diffusion process and reach the interface between the silicone rubber and FRP, which may cause the damage to the interface and also the change of PD properties under ac voltages. In our study, the PD properties in the interface before and after liquids permeation were measured by a PD measurement system. The liquids we chose in this study were three kinds, including deionized water, NaCl solution and HNO3 solution, since composite insulators encountered such kinds of liquids in practice. Since the permeation time for liquids was the key point, different values of PD were gained after several different days' permeation, which may reflect the deterioration process of the interface. Our PD research, together with the past test results about interface resistivity, could provide an in-depth understanding of the interface performance in composite insulators.
复合绝缘子中硅橡胶与纤维增强塑料界面局部放电的研究
一般来说,纤维增强塑料(FRP)和硅橡胶之间的内部宏观界面是整个复合保温系统的薄弱环节。水分的进入可能导致界面的附着力损失,甚至导致绝缘性能的显著下降。需要指出的是,目前缺乏对界面电性能的检测方法。本研究设计并制造了一种测量界面局部放电(PD)的电极系统。电极在固化过程中嵌入到界面中。我们知道,当复合绝缘子遇到液体时,液体可能通过扩散过程渗透到硅橡胶外壳中,到达硅橡胶与FRP之间的界面,从而造成界面的破坏,并在交流电压下改变PD性能。在我们的研究中,用PD测量系统测量了液体渗透前后界面的PD特性。由于复合绝缘子在实际使用中会遇到去离子水、NaCl溶液和HNO3溶液这三种液体,我们在本研究中选择了这三种液体。由于液体的渗透时间是关键点,不同时间的渗透得到不同的PD值,这可能反映了界面的恶化过程。我们的PD研究,结合以往的界面电阻率测试结果,可以深入了解复合绝缘子的界面性能。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信