{"title":"Battery condition management an important way to protect a critical asset","authors":"T. Churchill","doi":"10.1109/62.854023","DOIUrl":null,"url":null,"abstract":"The efficacy of employing battery condition management equipment and procedures is demonstrated on the solid basis of field experience in which the host batteries were found either to be flawed or operated in ways that would compromise reliability. Examples found using such equipment and reported in this paper include a cell whose voltage vacillated daily while on float, post/strap joints whose accept/reject connection integrity was erratic with time, chargers whose voltages were improperly set (both high and low), and a battery room environment whose conditions were life-shortening to electrolytic cells.","PeriodicalId":368992,"journal":{"name":"Fifteenth Annual Battery Conference on Applications and Advances (Cat. No.00TH8490)","volume":"73 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2000-01-11","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"4","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Fifteenth Annual Battery Conference on Applications and Advances (Cat. No.00TH8490)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/62.854023","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 4
Abstract
The efficacy of employing battery condition management equipment and procedures is demonstrated on the solid basis of field experience in which the host batteries were found either to be flawed or operated in ways that would compromise reliability. Examples found using such equipment and reported in this paper include a cell whose voltage vacillated daily while on float, post/strap joints whose accept/reject connection integrity was erratic with time, chargers whose voltages were improperly set (both high and low), and a battery room environment whose conditions were life-shortening to electrolytic cells.