Xiangshun Li, Hongliang He, Jiang-hua Lu, Z. Liang
{"title":"Modified Synchronous Reference Frame Method for Active Power Filter under Asymmetric and Distorted Supply Voltages Condition","authors":"Xiangshun Li, Hongliang He, Jiang-hua Lu, Z. Liang","doi":"10.1109/ICIICII.2015.88","DOIUrl":null,"url":null,"abstract":"In this paper, a modified harmonic and reactive current detection method based on synchronous reference frame (SRF) theory for three-phase four-wire shunt active power filter (SAPF) is proposed under distorted supply voltages condition. The main objective of the method is to extract the fundamental positive-sequence active currents, which can compensate the fundamental positive sequence reactive components, the unbalanced components and harmonics of the load currents. A model of three-phase four-leg SAPF with LCL-filter based on the proposed SRF method has been designed and simulated on MATLAB/simulink. Simulation results indicate that not only the current total harmonic distortion (THDi) values for each phase of the supply currents are reduced from 21.71%, 22.37% and 20.82% to 4.56%, 4.67% and 4.58%, but also the supply currents are balanced and sinusoidal after compensation.","PeriodicalId":349920,"journal":{"name":"2015 International Conference on Industrial Informatics - Computing Technology, Intelligent Technology, Industrial Information Integration","volume":"2 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2015-12-03","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"5","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2015 International Conference on Industrial Informatics - Computing Technology, Intelligent Technology, Industrial Information Integration","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ICIICII.2015.88","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 5
Abstract
In this paper, a modified harmonic and reactive current detection method based on synchronous reference frame (SRF) theory for three-phase four-wire shunt active power filter (SAPF) is proposed under distorted supply voltages condition. The main objective of the method is to extract the fundamental positive-sequence active currents, which can compensate the fundamental positive sequence reactive components, the unbalanced components and harmonics of the load currents. A model of three-phase four-leg SAPF with LCL-filter based on the proposed SRF method has been designed and simulated on MATLAB/simulink. Simulation results indicate that not only the current total harmonic distortion (THDi) values for each phase of the supply currents are reduced from 21.71%, 22.37% and 20.82% to 4.56%, 4.67% and 4.58%, but also the supply currents are balanced and sinusoidal after compensation.