{"title":"데이터 센터 및 건물 공조용 냉수코일의 종류에 따른 성능 특성에 관한 연구","authors":"Min-Geon Go, Byoung-Nam Choi, Hyung-Beom Seung","doi":"10.17958/ksmt.21.6.201912.1021","DOIUrl":null,"url":null,"abstract":"In this study, heat exchangers used in data center and building air-conditioners were tested according to the type of heat exchangers to select them for commercial use. The experiment was performed three samples, one micro channel heat exchanger, the same volume oval coil and the same performance oval coil. The experiment conducted under actual operation conditions in the data center and building. Micro-channel heat exchanger has lower air side pressure drop and higher capacity per volume than oval coil. It may be advantageous when the installation small space or the little design static pressure in the fan, such as in-row systems or CRAC installed in data center.","PeriodicalId":168106,"journal":{"name":"Journal of the Korean Society of Mechanical Technology","volume":"3 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2019-12-31","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Journal of the Korean Society of Mechanical Technology","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.17958/ksmt.21.6.201912.1021","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0
Abstract
In this study, heat exchangers used in data center and building air-conditioners were tested according to the type of heat exchangers to select them for commercial use. The experiment was performed three samples, one micro channel heat exchanger, the same volume oval coil and the same performance oval coil. The experiment conducted under actual operation conditions in the data center and building. Micro-channel heat exchanger has lower air side pressure drop and higher capacity per volume than oval coil. It may be advantageous when the installation small space or the little design static pressure in the fan, such as in-row systems or CRAC installed in data center.