{"title":"HVDC performance analysis according to ER-filter and single tuned filter","authors":"Chan-Ki Kim, Byeong-mo Yang, Yoo-Ho Kim, H. Rhew","doi":"10.1109/IECON.2003.1280667","DOIUrl":null,"url":null,"abstract":"This paper deals with the novel HVDC filter topology. The proposed method is the combination the active filter with ER-filter (energy recovery-filter). The active filter of the proposed method is a kind of hybrid filter, consists of the passive filter and the voltage source. Also, the single tuned active filter to eliminate 11/sup th//13/sup th/ harmonics is proposed. This proposed active filter is very useful to reduce the cost of the active filter. ER-filter is to return the filter power to AC network, used to replace with the damped filter. Consequently, PSCAD/EMTDC is used to investigate the validation of the proposed topology.","PeriodicalId":403239,"journal":{"name":"IECON'03. 29th Annual Conference of the IEEE Industrial Electronics Society (IEEE Cat. No.03CH37468)","volume":"87 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2003-11-02","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"3","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"IECON'03. 29th Annual Conference of the IEEE Industrial Electronics Society (IEEE Cat. No.03CH37468)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/IECON.2003.1280667","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 3
Abstract
This paper deals with the novel HVDC filter topology. The proposed method is the combination the active filter with ER-filter (energy recovery-filter). The active filter of the proposed method is a kind of hybrid filter, consists of the passive filter and the voltage source. Also, the single tuned active filter to eliminate 11/sup th//13/sup th/ harmonics is proposed. This proposed active filter is very useful to reduce the cost of the active filter. ER-filter is to return the filter power to AC network, used to replace with the damped filter. Consequently, PSCAD/EMTDC is used to investigate the validation of the proposed topology.