P. Toman, D. Topolanek, J. Orságová, J. Dvorak
{"title":"Experimental measuring of the touch voltages in large compensated networks","authors":"P. Toman, D. Topolanek, J. Orságová, J. Dvorak","doi":"10.1109/PQ.2012.6256227","DOIUrl":null,"url":null,"abstract":"A connection between a phase conductor and the ground in MV networks is called earth fault. The fault current in this case does not depend on the point of the fault, but only on the total capacity (size) of a network. Distribution system operator (DSO) sometimes needs to operate the large network which means operating of the network with big capacitive current (in Czech Republic more than 800A). This operation puts the emphasis not only on the setting of the earth fault relays but on the safety of the point of fault too. The paper describes the tests in real compensated distribution network with capacitive currents 300A and 800A. There were tested low-ohmic and arc fault. The first results show that the operation of large network is possible with using of the automatics of additional earthing of affected phase. The touch and step voltages were reduced under level allowed by standard EN 50522.","PeriodicalId":185013,"journal":{"name":"2012 Electric Power Quality and Supply Reliability","volume":"4 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2012-06-11","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"2","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2012 Electric Power Quality and Supply Reliability","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/PQ.2012.6256227","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 2

Abstract

A connection between a phase conductor and the ground in MV networks is called earth fault. The fault current in this case does not depend on the point of the fault, but only on the total capacity (size) of a network. Distribution system operator (DSO) sometimes needs to operate the large network which means operating of the network with big capacitive current (in Czech Republic more than 800A). This operation puts the emphasis not only on the setting of the earth fault relays but on the safety of the point of fault too. The paper describes the tests in real compensated distribution network with capacitive currents 300A and 800A. There were tested low-ohmic and arc fault. The first results show that the operation of large network is possible with using of the automatics of additional earthing of affected phase. The touch and step voltages were reduced under level allowed by standard EN 50522.
大型补偿网络中接触电压的实验测量
中压网络中相导体与地之间的连接称为接地故障。这种情况下的故障电流与故障点无关,只与网络的总容量(大小)有关。配电系统运营商(DSO)有时需要运行大电网,这意味着运行大容电流的电网(在捷克超过800A)。这种操作不仅强调了接地故障继电器的设置,而且也强调了故障点的安全性。本文介绍了电容电流为300A和800A的实际补偿配电网的试验情况。测试了低欧姆和电弧故障。初步结果表明,利用受影响相位附加接地的自动装置,大电网的运行是可能的。触摸电压和步进电压被降低到EN 50522标准允许的水平以下。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:604180095
Book学术官方微信