{"title":"A new control method in PV grid connected inverters for anti-islanding protection by impedance monitoring","authors":"Mohsen Hamzeh, S. Farhangi, B. Farhangi","doi":"10.1109/COMPEL.2008.4634664","DOIUrl":null,"url":null,"abstract":"This paper proposes a new control method for the single phase PV grid connected inverters. The proposed method injects interharmonic test current for measuring the impedance of the public grid to detect islanding situation. The proposed control system employs two PI controllers to generate the reference current separately for the fundamental frequency and interharmonic current, and finally applies a dead beat predictive control to determine the duty cycle of the switches. The grid impedance is measured simultaneously with injection of the interharmonic current using DFT algorithm.","PeriodicalId":156338,"journal":{"name":"2008 11th Workshop on Control and Modeling for Power Electronics","volume":"71 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2008-09-26","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"43","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2008 11th Workshop on Control and Modeling for Power Electronics","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/COMPEL.2008.4634664","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 43
Abstract
This paper proposes a new control method for the single phase PV grid connected inverters. The proposed method injects interharmonic test current for measuring the impedance of the public grid to detect islanding situation. The proposed control system employs two PI controllers to generate the reference current separately for the fundamental frequency and interharmonic current, and finally applies a dead beat predictive control to determine the duty cycle of the switches. The grid impedance is measured simultaneously with injection of the interharmonic current using DFT algorithm.