{"title":"On the no-load loss of power transformers under voltages with sub-harmonics","authors":"E. Arslan, S. Sakar, M. Balci","doi":"10.1109/ENERGYCON.2014.6850433","DOIUrl":null,"url":null,"abstract":"Power transformers are traditionally designed for their utilization in sinusoidal voltage and current conditions. However, the non-linear loads are largely proliferated in the modern power systems. Thus, pec (point of common coupling) voltages and line currents usually have harmonically distorted or non-sinusoidal waveshapes. This study focuses on the parametrical analysis of transformer no-load loss under the excitation voltage with several sub-harmonic contents. For this aim, a computationally efficient technique is developed by combining both the harmonic-domain model of transformer windings and Finite Element Method (FEM) based modeling of transformer core. The obtained simulation results figured out that effect of sub-harmonic voltages on the transformer core loss is negligible. However, it is also seen that small amount of sub-harmonic voltages may highly contribute the winding loss under the no-load condition, and they should carefully be handled for the derating of power transformers.","PeriodicalId":410611,"journal":{"name":"2014 IEEE International Energy Conference (ENERGYCON)","volume":"13 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2014-05-13","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"11","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2014 IEEE International Energy Conference (ENERGYCON)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ENERGYCON.2014.6850433","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 11
Abstract
Power transformers are traditionally designed for their utilization in sinusoidal voltage and current conditions. However, the non-linear loads are largely proliferated in the modern power systems. Thus, pec (point of common coupling) voltages and line currents usually have harmonically distorted or non-sinusoidal waveshapes. This study focuses on the parametrical analysis of transformer no-load loss under the excitation voltage with several sub-harmonic contents. For this aim, a computationally efficient technique is developed by combining both the harmonic-domain model of transformer windings and Finite Element Method (FEM) based modeling of transformer core. The obtained simulation results figured out that effect of sub-harmonic voltages on the transformer core loss is negligible. However, it is also seen that small amount of sub-harmonic voltages may highly contribute the winding loss under the no-load condition, and they should carefully be handled for the derating of power transformers.