Improving the airtightness of existing plasterboard-lined load-bearing masonry dwellings

D. Johnston, R. Lowe
{"title":"Improving the airtightness of existing plasterboard-lined load-bearing masonry dwellings","authors":"D. Johnston, R. Lowe","doi":"10.1191/0143624406bt135oa","DOIUrl":null,"url":null,"abstract":"This paper describes an approach that has been undertaken to improve the airtightness of a number of plasterboard-lined load-bearing masonry dwellings that were constructed in the early 1970s. Such dwellings are likely to be broadly representative of many of the dwellings that will be refurbished in the UK over the next decade or so. The airtightness of the dwellings was improved by undertaking a two-stage programme of general and targeted airtightness work, in parallel with a basic domestic refurbishment programme. The results illustrate that prior to the refurbishment, the dwellings were in a poor state of repair and had an air permeability of between 24 and 26 m3/h per m2 at 50 Pa, which is substantially in excess of the UK mean of 11.5 m3/h per m2 at 50 Pa.1 The condition of the dwellings also suggests that the air permeability of these dwellings is likely to be considerably higher than that which would have been experienced when they were first built. Following the refurbishment programme, it was possible to reduce the air permeability of these dwellings by almost 55%, to a mean of just over 11 m3/h per m2 at 50 Pa. The paper also identifies a number of factors that limited the effectiveness of the airtightness work. These factors included: wear and tear of the plasterboard-lining; detailing and workmanship during the refurbishment programme; and, the partial nature of the refurbishment programme. Had it been possible to address a number of these factors during the refurbishment programme, the authors are reasonably confident that an air permeability of less than 10 m3/h per m2 at 50 Pa could have been achieved in all of the dwellings. Despite the small size of the sample (only 12 dwellings were tested), the results suggest that the airtightness of existing plasterboard-lined load-bearing masonry dwellings can be improved to a level that is comparable to the current UK Building Regulations (Approved Document Part L1) requirement for new dwellings.2 Practical application: Airtightness is crucial to improving the energy performance of buildings. In the UK, existing dwellings tend to be very leaky compared to some of their international counterparts. The use of plasterboard-lining as an internal finish to external and party walls makes a significant contribution to this poor performance, particularly where it is not edge sealed. Air leakage measurements reported here for dwellings built in the 1970s suggest that if this construction is allowed to deteriorate, very high leakage rates may result. Considerations of the impact of choice of construction on future robustness and durability of airtightness of new housing is likely to be an important practicalconsideration, particularly for social housing providers. Separating the air barrier function from the plasterboard lining appears to provide a more reliable and probably more durable solution.3 The paper goes on to describe how injecting expanding polyurethane foam into the cavity between the inner leaf of blockwork and the plasterboard-lining to form continuous ribbons of foam can seal the plasterboard lining and prevent air movement within this cavity. If this approach is undertaken in parallel with a domestic refurbishment programme, the air leakage rate of existing plasterboard-lined masonry cavity dwellings was shown to be reduced to a level comparable with the requirements of the current Part L1 for new dwellings.","PeriodicalId":272488,"journal":{"name":"Building Services Engineering Research and Technology","volume":"16 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2006-02-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"11","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"Building Services Engineering Research and Technology","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1191/0143624406bt135oa","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 11

Abstract

This paper describes an approach that has been undertaken to improve the airtightness of a number of plasterboard-lined load-bearing masonry dwellings that were constructed in the early 1970s. Such dwellings are likely to be broadly representative of many of the dwellings that will be refurbished in the UK over the next decade or so. The airtightness of the dwellings was improved by undertaking a two-stage programme of general and targeted airtightness work, in parallel with a basic domestic refurbishment programme. The results illustrate that prior to the refurbishment, the dwellings were in a poor state of repair and had an air permeability of between 24 and 26 m3/h per m2 at 50 Pa, which is substantially in excess of the UK mean of 11.5 m3/h per m2 at 50 Pa.1 The condition of the dwellings also suggests that the air permeability of these dwellings is likely to be considerably higher than that which would have been experienced when they were first built. Following the refurbishment programme, it was possible to reduce the air permeability of these dwellings by almost 55%, to a mean of just over 11 m3/h per m2 at 50 Pa. The paper also identifies a number of factors that limited the effectiveness of the airtightness work. These factors included: wear and tear of the plasterboard-lining; detailing and workmanship during the refurbishment programme; and, the partial nature of the refurbishment programme. Had it been possible to address a number of these factors during the refurbishment programme, the authors are reasonably confident that an air permeability of less than 10 m3/h per m2 at 50 Pa could have been achieved in all of the dwellings. Despite the small size of the sample (only 12 dwellings were tested), the results suggest that the airtightness of existing plasterboard-lined load-bearing masonry dwellings can be improved to a level that is comparable to the current UK Building Regulations (Approved Document Part L1) requirement for new dwellings.2 Practical application: Airtightness is crucial to improving the energy performance of buildings. In the UK, existing dwellings tend to be very leaky compared to some of their international counterparts. The use of plasterboard-lining as an internal finish to external and party walls makes a significant contribution to this poor performance, particularly where it is not edge sealed. Air leakage measurements reported here for dwellings built in the 1970s suggest that if this construction is allowed to deteriorate, very high leakage rates may result. Considerations of the impact of choice of construction on future robustness and durability of airtightness of new housing is likely to be an important practicalconsideration, particularly for social housing providers. Separating the air barrier function from the plasterboard lining appears to provide a more reliable and probably more durable solution.3 The paper goes on to describe how injecting expanding polyurethane foam into the cavity between the inner leaf of blockwork and the plasterboard-lining to form continuous ribbons of foam can seal the plasterboard lining and prevent air movement within this cavity. If this approach is undertaken in parallel with a domestic refurbishment programme, the air leakage rate of existing plasterboard-lined masonry cavity dwellings was shown to be reduced to a level comparable with the requirements of the current Part L1 for new dwellings.
改善现有石膏板内衬承重砌体住宅的气密性
本文描述了一种改善20世纪70年代早期建造的石膏板内衬承重砖石住宅气密性的方法。这样的住宅很可能是未来十年左右英国将翻新的许多住宅的广泛代表。住宅的密闭性得到了改善,办法是进行两阶段的一般和有针对性的密闭性工作方案,同时进行基本的国内翻新方案。结果说明在翻新之前,居住在一个贫穷的国家之间的修复和透气性有24和26立方米/小时每平方米50 Pa,这是大大超过英国平均每平方米11.5 m3 / h在50岁Pa.1住处的情况也表明,这些住宅的透气性可能会大大高于那些经验丰富的初建时。在翻新计划之后,这些住宅的透气性可以降低近55%,在50 Pa的条件下,平均每平方米的透气性略高于11 m3/h。本文还指出了一些限制气密性工作有效性的因素。这些因素包括:石膏板衬里的磨损;翻新计划中的细节和工艺;此外,翻新计划的局部性质。如果在翻新计划中能够解决其中的一些因素,作者有理由相信,在50 Pa的条件下,所有住宅的透气性都可以达到每平方米10立方米/小时以下。尽管样本规模很小(仅测试了12个住宅),但结果表明,现有石膏板内衬承重砌体住宅的气密性可以提高到与当前英国建筑法规(批准文件第L1部分)对新住宅的要求相当的水平实际应用:密封性对提高建筑物的能源性能至关重要。与一些国际同行相比,英国现有的住宅往往非常漏水。使用石膏板衬里作为外部和方墙的内部饰面,对这种糟糕的性能做出了重大贡献,特别是在没有边缘密封的情况下。这里报告的20世纪70年代建造的住宅的空气泄漏测量表明,如果允许这种建筑恶化,可能会导致非常高的泄漏率。考虑建筑的选择对新住房未来的坚固性和密封性的耐久性的影响可能是一个重要的实际考虑,特别是对于社会住房提供者。将空气屏障功能与石膏板衬里分离似乎提供了一种更可靠、可能更持久的解决方案本文接着描述了如何将膨胀的聚氨酯泡沫注入砌块内叶与石膏板衬里之间的空腔中,形成连续的泡沫带,以密封石膏板衬里,并防止该空腔内的空气流动。如果这一方法与住宅翻新计划同时进行,现有石膏板砌筑空心住宅的漏风率将降低到与目前第L1部分对新住宅的要求相当的水平。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信