Current Amplitude Ratio Based Pilot Protection for the transmission Line Connected to Inverter-interfaced Renewable Energy Power Plants

K. Jia, Zhe Yang, Zhengxuan Zhu, Yu Fang, Qijuan Zhao, Bohan Liu
{"title":"Current Amplitude Ratio Based Pilot Protection for the transmission Line Connected to Inverter-interfaced Renewable Energy Power Plants","authors":"K. Jia, Zhe Yang, Zhengxuan Zhu, Yu Fang, Qijuan Zhao, Bohan Liu","doi":"10.1109/ISGT-Asia.2019.8881746","DOIUrl":null,"url":null,"abstract":"The internal impedance of inverter-interfaced renewable energy generators (IIREGs) is unstable and its phase angle is affected by control systems, so the ratio braking style differential protection faces great challenges. To solve this problem, a pilot protection method based on current amplitude ratio on both sides is proposed. The method only needs to transmit the scalar signal which reduces the requirements on the communication system and synchronizing ability. It can operate correctly in the case of reclosing on permanent faults and weak output of the power plants. In addition, its principle is simple and reliable, and only requires a conventional sampling frequency and a computation speed. These features make it become a good choice for industrial application. The simulation results show that the protection method can correctly distinguish internal and external faults and field-testing data also confirm the effectiveness of the method.","PeriodicalId":257974,"journal":{"name":"2019 IEEE Innovative Smart Grid Technologies - Asia (ISGT Asia)","volume":"17 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2019-05-21","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"9","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2019 IEEE Innovative Smart Grid Technologies - Asia (ISGT Asia)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ISGT-Asia.2019.8881746","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 9

Abstract

The internal impedance of inverter-interfaced renewable energy generators (IIREGs) is unstable and its phase angle is affected by control systems, so the ratio braking style differential protection faces great challenges. To solve this problem, a pilot protection method based on current amplitude ratio on both sides is proposed. The method only needs to transmit the scalar signal which reduces the requirements on the communication system and synchronizing ability. It can operate correctly in the case of reclosing on permanent faults and weak output of the power plants. In addition, its principle is simple and reliable, and only requires a conventional sampling frequency and a computation speed. These features make it become a good choice for industrial application. The simulation results show that the protection method can correctly distinguish internal and external faults and field-testing data also confirm the effectiveness of the method.
基于电流幅值比的可再生能源发电厂与逆变器接口的传输线导频保护
逆变器接口可再生能源发电机(IIREGs)的内部阻抗不稳定,相位角受控制系统的影响,使得比率制动式差动保护面临很大的挑战。针对这一问题,提出了一种基于两侧电流幅值比的导频保护方法。该方法只需要传输标量信号,降低了对通信系统和同步能力的要求。在电厂永久故障重合闸和输出微弱的情况下,该装置仍能正常运行。其原理简单可靠,只需要常规的采样频率和一定的计算速度即可。这些特点使其成为工业应用的良好选择。仿真结果表明,该保护方法能够正确区分内部故障和外部故障,现场测试数据也证实了该方法的有效性。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信