Two-phase mini-thermosyphon electronics cooling, Part 2: Model and steady-state validations

J. Marcinichen, N. Lamaison, C. L. Ong, J. Thome
{"title":"Two-phase mini-thermosyphon electronics cooling, Part 2: Model and steady-state validations","authors":"J. Marcinichen, N. Lamaison, C. L. Ong, J. Thome","doi":"10.1109/ITHERM.2016.7517600","DOIUrl":null,"url":null,"abstract":"In the present study, a simulation code specifically developed to evaluate the thermal-hydraulic performance of thermosyphon cooling loops is validated through the experimental results obtained in the Part 1. It considers levels of heat load conventionally observed in real servers of datacenters, which means idle, normal and maximum clock speed of actual microprocessors. The thermosyphon is a very compact unit with a height of 15 cm and capable of safely operating up to a heat flux of 80 W cm-2. The loop basically is comprised of a riser, a downcomer, a micro-evaporator and a counter flow tube-in-tube condenser. The latter is cooled by cold water whose mass flow rate can be controlled through an external pump (speed control), so that parameters such as saturation temperature and/or condenser outlet subcooling can be adjusted for a pre-defined set point, and thus increasing the range of operability of the cooling loop. Other parameters were also explored experimentally, cooling looping overall performance, chip (junction) temperature, whilst the critical heat flux was estimated from a leading CHF method. Finally, the study showed that the passive two-phase closed loop thermosyphon cooling system is a safe and energetically viable technology solution for the next generation of datacenters.","PeriodicalId":426908,"journal":{"name":"2016 15th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm)","volume":"143 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2016-05-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"8","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2016 15th IEEE Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ITHERM.2016.7517600","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 8

Abstract

In the present study, a simulation code specifically developed to evaluate the thermal-hydraulic performance of thermosyphon cooling loops is validated through the experimental results obtained in the Part 1. It considers levels of heat load conventionally observed in real servers of datacenters, which means idle, normal and maximum clock speed of actual microprocessors. The thermosyphon is a very compact unit with a height of 15 cm and capable of safely operating up to a heat flux of 80 W cm-2. The loop basically is comprised of a riser, a downcomer, a micro-evaporator and a counter flow tube-in-tube condenser. The latter is cooled by cold water whose mass flow rate can be controlled through an external pump (speed control), so that parameters such as saturation temperature and/or condenser outlet subcooling can be adjusted for a pre-defined set point, and thus increasing the range of operability of the cooling loop. Other parameters were also explored experimentally, cooling looping overall performance, chip (junction) temperature, whilst the critical heat flux was estimated from a leading CHF method. Finally, the study showed that the passive two-phase closed loop thermosyphon cooling system is a safe and energetically viable technology solution for the next generation of datacenters.
两相微型热虹吸电子冷却,第2部分:模型和稳态验证
在本研究中,通过第一部分的实验结果验证了专门用于评估热虹吸冷却回路热工性能的仿真代码。它考虑了在数据中心的实际服务器中通常观察到的热负荷水平,这意味着实际微处理器的空闲、正常和最大时钟速度。热虹吸是一个非常紧凑的单元,高度为15厘米,能够安全运行到80w cm-2的热流。该回路基本上由一个上升管、一个下降管、一个微型蒸发器和一个逆流管中冷凝器组成。后者由冷水冷却,冷水的质量流量可以通过外部泵(速度控制)来控制,因此,诸如饱和温度和/或冷凝器出口过冷等参数可以调整到预定义的设定点,从而增加了冷却回路的可操作性范围。其他参数也进行了实验探索,冷却回路的整体性能,芯片(结)温度,而临界热流由一个领先的CHF方法估计。最后,研究表明,被动两相闭环热虹吸冷却系统是下一代数据中心安全且节能可行的技术解决方案。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信