Parameters measurement for grounding grids of a 1000kV ultra-high-voltage substation

Si Wen-rong, Fu Chen-zhao, Lu Bing-Bing, Guo Xiang, Xu Zhi-Bing
{"title":"Parameters measurement for grounding grids of a 1000kV ultra-high-voltage substation","authors":"Si Wen-rong, Fu Chen-zhao, Lu Bing-Bing, Guo Xiang, Xu Zhi-Bing","doi":"10.1109/TENCON.2016.7848746","DOIUrl":null,"url":null,"abstract":"In this paper, taking parameters measurement for grounding grids of the 1000kV ultra-high-voltage (UHV) Suzhou substation as an example, it introduces the basic situation about the designed grounding grids, the methods used to measure the power frequency (50 Hz) ground resistance (PFGR) and impulse grounding impedance (IGI), respectively. The PFGR data are analyzed and checked which were measured using the non-50Hz-frequency current method with two different instruments. While the measurement of IGI was realized using a small and portable instrument, which can output the 8/20 µs or 10/350 µs lightning currents with simultaneously recording the corresponding voltage waveforms from the grounding grids. All of work accumulated the engineering experience of the on-site test and parameters measurement technology for the grounding grids of 1000kV UHV substations.","PeriodicalId":246458,"journal":{"name":"2016 IEEE Region 10 Conference (TENCON)","volume":"1 1","pages":"0"},"PeriodicalIF":0.0000,"publicationDate":"2016-11-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"1","resultStr":null,"platform":"Semanticscholar","paperid":null,"PeriodicalName":"2016 IEEE Region 10 Conference (TENCON)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/TENCON.2016.7848746","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 1

Abstract

In this paper, taking parameters measurement for grounding grids of the 1000kV ultra-high-voltage (UHV) Suzhou substation as an example, it introduces the basic situation about the designed grounding grids, the methods used to measure the power frequency (50 Hz) ground resistance (PFGR) and impulse grounding impedance (IGI), respectively. The PFGR data are analyzed and checked which were measured using the non-50Hz-frequency current method with two different instruments. While the measurement of IGI was realized using a small and portable instrument, which can output the 8/20 µs or 10/350 µs lightning currents with simultaneously recording the corresponding voltage waveforms from the grounding grids. All of work accumulated the engineering experience of the on-site test and parameters measurement technology for the grounding grids of 1000kV UHV substations.
1000kV超高压变电站接地网参数测量
本文以苏州1000kV特高压变电站接地网参数测量为例,介绍了所设计接地网的基本情况、工频(50hz)接地电阻(PFGR)和冲击接地阻抗(IGI)的测量方法。对采用非50hz频率电流法测量的PFGR数据进行了分析和校核。而IGI的测量则是使用小型便携式仪器实现的,该仪器可以输出8/20µs或10/350µs雷电电流,同时记录接地网相应的电压波形。积累了1000kV特高压变电站接地网现场试验及参数测量技术的工程经验。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
求助全文
约1分钟内获得全文 求助全文
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信