喷射风机通风系统对喷头启动的影响

P.A. (Tony) Enright
{"title":"喷射风机通风系统对喷头启动的影响","authors":"P.A. (Tony) Enright","doi":"10.1016/j.csfs.2013.11.002","DOIUrl":null,"url":null,"abstract":"<div><p>Jet fans are increasingly preferred over traditional ducted systems as a means of ventilating pollutants from large spaces such as car parking buildings.</p><p>Outside of tunnel applications jet fans are considered to have limitations as means of smoke control. This is because their effectiveness is limited without side walls and they de-stratify the smoke layer. Jet fans can however, aid post-event in smoke clearance under the control of the attending fire brigade.</p><p>The prudent fire mode strategy in those jurisdictions where jet fans are not used for smoke control is for the ventilation system to shut down on a fire alarm signal.</p><p>The problem lies in the jet fans receiving that signal. A fire has three basic signatures; heat, smoke, and light.</p><p>Large car parking buildings may be sprinkler-protected. Sprinklers operate on the heat signature. A jet fan is assumed to disrupt this signature by forcing the plume of heat downstream and diluting that plume with cool air. This may delay sprinkler activation.</p><p>In terms of the smoke signature, the presence of pollutants such as carbon monoxide that could be detected by a specialised detector, are the same signals that would cause a jet fan to increase its flow in normal mode. The response to a smoke signature is contradictory between the desired normal-mode reaction to speed up and the fire-mode reaction to shut down.</p><p>This leaves light. Fires are very rich across the non-visible light spectra and flame detectors are an effective way to provide a fire signal independent of the normal-mode operation of the jet fans. However, the cost-benefit of installing flame detectors in addition to sprinklers is questionable.</p><p>A series of detailed computational analyses are therefore undertaken to quantify the impact of the jet fans on delaying sprinkler activation on a typical car park sprinkler arrangement. This article assumes the perspective of a jurisdiction where the fire mode strategy is for the fans to shut down. However, the sprinkler delay will also be of interest where the fire mode strategy is to continue operating.</p><p>Once sprinkler activation had occurred a fire signal is assumed to have been generated to shut down the jet fans. Separate evaluations can then be made as to whether the delay was acceptable or not, dependent upon to the specific building geometry.</p><p>The results indicate that for a fast-growing design fire, sprinkler activation occurred at ∼180<!--> <!-->s with the jet fans off and at ∼210<!--> <!-->s with them on: an increase of ⩽30<!--> <!-->s. A separate analysis was undertaken for the case-specific egress safety margin. Comparing the two, it was concluded, that the impact of jet fans upon sprinkler activation was not significant. It was further established that the smoke disturbance due to the jet fan flow did not adversely affect the visibility for those escaping.</p></div>","PeriodicalId":100219,"journal":{"name":"Case Studies in Fire Safety","volume":null,"pages":null},"PeriodicalIF":0.0000,"publicationDate":"2014-03-01","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"https://sci-hub-pdf.com/10.1016/j.csfs.2013.11.002","citationCount":"15","resultStr":"{\"title\":\"Impact of jet fan ventilation systems on sprinkler activation\",\"authors\":\"P.A. (Tony) Enright\",\"doi\":\"10.1016/j.csfs.2013.11.002\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"<div><p>Jet fans are increasingly preferred over traditional ducted systems as a means of ventilating pollutants from large spaces such as car parking buildings.</p><p>Outside of tunnel applications jet fans are considered to have limitations as means of smoke control. This is because their effectiveness is limited without side walls and they de-stratify the smoke layer. Jet fans can however, aid post-event in smoke clearance under the control of the attending fire brigade.</p><p>The prudent fire mode strategy in those jurisdictions where jet fans are not used for smoke control is for the ventilation system to shut down on a fire alarm signal.</p><p>The problem lies in the jet fans receiving that signal. A fire has three basic signatures; heat, smoke, and light.</p><p>Large car parking buildings may be sprinkler-protected. Sprinklers operate on the heat signature. A jet fan is assumed to disrupt this signature by forcing the plume of heat downstream and diluting that plume with cool air. This may delay sprinkler activation.</p><p>In terms of the smoke signature, the presence of pollutants such as carbon monoxide that could be detected by a specialised detector, are the same signals that would cause a jet fan to increase its flow in normal mode. The response to a smoke signature is contradictory between the desired normal-mode reaction to speed up and the fire-mode reaction to shut down.</p><p>This leaves light. Fires are very rich across the non-visible light spectra and flame detectors are an effective way to provide a fire signal independent of the normal-mode operation of the jet fans. However, the cost-benefit of installing flame detectors in addition to sprinklers is questionable.</p><p>A series of detailed computational analyses are therefore undertaken to quantify the impact of the jet fans on delaying sprinkler activation on a typical car park sprinkler arrangement. This article assumes the perspective of a jurisdiction where the fire mode strategy is for the fans to shut down. However, the sprinkler delay will also be of interest where the fire mode strategy is to continue operating.</p><p>Once sprinkler activation had occurred a fire signal is assumed to have been generated to shut down the jet fans. Separate evaluations can then be made as to whether the delay was acceptable or not, dependent upon to the specific building geometry.</p><p>The results indicate that for a fast-growing design fire, sprinkler activation occurred at ∼180<!--> <!-->s with the jet fans off and at ∼210<!--> <!-->s with them on: an increase of ⩽30<!--> <!-->s. A separate analysis was undertaken for the case-specific egress safety margin. Comparing the two, it was concluded, that the impact of jet fans upon sprinkler activation was not significant. It was further established that the smoke disturbance due to the jet fan flow did not adversely affect the visibility for those escaping.</p></div>\",\"PeriodicalId\":100219,\"journal\":{\"name\":\"Case Studies in Fire Safety\",\"volume\":null,\"pages\":null},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2014-03-01\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"https://sci-hub-pdf.com/10.1016/j.csfs.2013.11.002\",\"citationCount\":\"15\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Case Studies in Fire Safety\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://www.sciencedirect.com/science/article/pii/S2214398X13000034\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Case Studies in Fire Safety","FirstCategoryId":"1085","ListUrlMain":"https://www.sciencedirect.com/science/article/pii/S2214398X13000034","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 15

摘要

相对于传统的管道系统,喷气风扇越来越受到人们的青睐,作为一种将污染物从停车场等大空间排出的方式。在隧道应用之外,射流风机作为烟雾控制手段被认为有局限性。这是因为他们的效力是有限的,没有侧壁,他们去分层烟层。然而,喷气式风扇可以在参加活动的消防队的控制下帮助清除烟雾。在那些不使用喷气风扇控制烟雾的地区,谨慎的消防模式策略是在火灾报警信号时关闭通风系统。问题在于接收信号的喷气风扇。火有三个基本特征;热,烟,光。大型停车场可能有洒水装置保护。洒水喷头根据热信号工作。据推测,喷气风扇通过迫使热量羽流向下游流动,并用冷空气稀释羽流来破坏这一特征。这可能会延迟喷头的启动。就烟雾特征而言,可以由专门的探测器检测到的一氧化碳等污染物的存在,与导致喷气风扇在正常模式下增加流量的信号相同。对烟雾特征的反应在期望的正常模式反应(加速)和火模式反应(关闭)之间是矛盾的。这留下了光。火焰在非可见光光谱中非常丰富,火焰探测器是一种有效的方法,可以提供独立于喷气风扇正常模式操作的火焰信号。然而,除了洒水装置外,安装火焰探测器的成本效益是值得怀疑的。因此,对典型的停车场洒水装置进行了一系列详细的计算分析,以量化喷射风扇对延迟洒水装置启动的影响。本文假设一个司法管辖区的视角,其中fire模式策略是让粉丝关闭。然而,在消防模式策略继续运行的情况下,喷头延迟也将引起人们的兴趣。一旦自动喷水灭火装置启动,就会产生一个火警信号来关闭喷射风扇。然后,根据具体的建筑几何形状,可以对延迟是否可以接受进行单独的评估。结果表明,对于快速燃烧的设计火灾,喷雾器的激活发生在关闭喷射风扇时的~ 180秒和打开喷射风扇时的~ 210秒:增加了≤30秒。对特定病例的出口安全裕度进行了单独分析。结果表明,射流风机对喷头激活的影响不显著。进一步确定了由射流风扇流引起的烟雾干扰不会对逃逸者的能见度产生不利影响。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Impact of jet fan ventilation systems on sprinkler activation

Jet fans are increasingly preferred over traditional ducted systems as a means of ventilating pollutants from large spaces such as car parking buildings.

Outside of tunnel applications jet fans are considered to have limitations as means of smoke control. This is because their effectiveness is limited without side walls and they de-stratify the smoke layer. Jet fans can however, aid post-event in smoke clearance under the control of the attending fire brigade.

The prudent fire mode strategy in those jurisdictions where jet fans are not used for smoke control is for the ventilation system to shut down on a fire alarm signal.

The problem lies in the jet fans receiving that signal. A fire has three basic signatures; heat, smoke, and light.

Large car parking buildings may be sprinkler-protected. Sprinklers operate on the heat signature. A jet fan is assumed to disrupt this signature by forcing the plume of heat downstream and diluting that plume with cool air. This may delay sprinkler activation.

In terms of the smoke signature, the presence of pollutants such as carbon monoxide that could be detected by a specialised detector, are the same signals that would cause a jet fan to increase its flow in normal mode. The response to a smoke signature is contradictory between the desired normal-mode reaction to speed up and the fire-mode reaction to shut down.

This leaves light. Fires are very rich across the non-visible light spectra and flame detectors are an effective way to provide a fire signal independent of the normal-mode operation of the jet fans. However, the cost-benefit of installing flame detectors in addition to sprinklers is questionable.

A series of detailed computational analyses are therefore undertaken to quantify the impact of the jet fans on delaying sprinkler activation on a typical car park sprinkler arrangement. This article assumes the perspective of a jurisdiction where the fire mode strategy is for the fans to shut down. However, the sprinkler delay will also be of interest where the fire mode strategy is to continue operating.

Once sprinkler activation had occurred a fire signal is assumed to have been generated to shut down the jet fans. Separate evaluations can then be made as to whether the delay was acceptable or not, dependent upon to the specific building geometry.

The results indicate that for a fast-growing design fire, sprinkler activation occurred at ∼180 s with the jet fans off and at ∼210 s with them on: an increase of ⩽30 s. A separate analysis was undertaken for the case-specific egress safety margin. Comparing the two, it was concluded, that the impact of jet fans upon sprinkler activation was not significant. It was further established that the smoke disturbance due to the jet fan flow did not adversely affect the visibility for those escaping.

求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信