{"title":"正确密封冷通道密封系统的好处","authors":"Yasin U. Makwana, Andrew R. Calder, S. Shrivastava","doi":"10.1109/ITHERM.2014.6892362","DOIUrl":null,"url":null,"abstract":"Data centers are mission-critical facilities and the nerve center of successful business operations. Surging demand for processing power, work load virtualization and consolidation is increasing data center heat loads, making the thermal management of data centers challenging. Containing the air in a data center is an important energy savings strategy towards data center optimization. Most of the modern, energy efficient, data centers deploy some kind of containment system. This paper discusses test data for a Cold Aisle Containment (CAC) system and compares it with a standard Hot Aisle/Cold Aisle (HA/CA) configuration. The HA/CA configuration is shown to support a heat load of 14.6kW/cabinet while the CAC system was tested up to 25.2 kW/cabinet. In addition, the test data demonstrated the cooling energy savings with the CAC system. Furthermore, we quantified the importance and effectiveness of sealing accessories (i.e. grommets for cable openings and blanking panels) when deployed in a CAC environment.","PeriodicalId":12453,"journal":{"name":"Fourteenth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm)","volume":"76 1","pages":"793-797"},"PeriodicalIF":0.0000,"publicationDate":"2014-05-27","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"19","resultStr":"{\"title\":\"Benefits of properly sealing a cold aisle containment system\",\"authors\":\"Yasin U. Makwana, Andrew R. Calder, S. Shrivastava\",\"doi\":\"10.1109/ITHERM.2014.6892362\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"Data centers are mission-critical facilities and the nerve center of successful business operations. Surging demand for processing power, work load virtualization and consolidation is increasing data center heat loads, making the thermal management of data centers challenging. Containing the air in a data center is an important energy savings strategy towards data center optimization. Most of the modern, energy efficient, data centers deploy some kind of containment system. This paper discusses test data for a Cold Aisle Containment (CAC) system and compares it with a standard Hot Aisle/Cold Aisle (HA/CA) configuration. The HA/CA configuration is shown to support a heat load of 14.6kW/cabinet while the CAC system was tested up to 25.2 kW/cabinet. In addition, the test data demonstrated the cooling energy savings with the CAC system. Furthermore, we quantified the importance and effectiveness of sealing accessories (i.e. grommets for cable openings and blanking panels) when deployed in a CAC environment.\",\"PeriodicalId\":12453,\"journal\":{\"name\":\"Fourteenth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm)\",\"volume\":\"76 1\",\"pages\":\"793-797\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2014-05-27\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"19\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Fourteenth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/ITHERM.2014.6892362\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Fourteenth Intersociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/ITHERM.2014.6892362","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 19

摘要

数据中心是关键任务设施,是成功业务运营的神经中枢。对处理能力、工作负载虚拟化和整合的需求激增,增加了数据中心的热负荷,使数据中心的热管理具有挑战性。在数据中心中包含空气是数据中心优化的重要节能策略。大多数现代、节能的数据中心都部署了某种密封系统。本文讨论了冷通道密封(CAC)系统的测试数据,并将其与标准的热通道/冷通道(HA/CA)配置进行了比较。HA/CA配置显示支持14.6kW/机柜的热负荷,而CAC系统测试的热负荷高达25.2 kW/机柜。此外,测试数据也证明了CAC系统的制冷节能效果。此外,我们量化了密封附件(即电缆开口和落料板的密封圈)在CAC环境中部署时的重要性和有效性。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Benefits of properly sealing a cold aisle containment system
Data centers are mission-critical facilities and the nerve center of successful business operations. Surging demand for processing power, work load virtualization and consolidation is increasing data center heat loads, making the thermal management of data centers challenging. Containing the air in a data center is an important energy savings strategy towards data center optimization. Most of the modern, energy efficient, data centers deploy some kind of containment system. This paper discusses test data for a Cold Aisle Containment (CAC) system and compares it with a standard Hot Aisle/Cold Aisle (HA/CA) configuration. The HA/CA configuration is shown to support a heat load of 14.6kW/cabinet while the CAC system was tested up to 25.2 kW/cabinet. In addition, the test data demonstrated the cooling energy savings with the CAC system. Furthermore, we quantified the importance and effectiveness of sealing accessories (i.e. grommets for cable openings and blanking panels) when deployed in a CAC environment.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信