{"title":"孟加拉国高压输电线路故障分析:巴拉普库里亚至比比亚纳","authors":"A. Gupta, Hisham-Al-Rashid, Md. Zahidul Anam, Mohaimenul Islam","doi":"10.1109/TENSYMP50017.2020.9230798","DOIUrl":null,"url":null,"abstract":"This paper reports a study on fault analysis on high voltage transmission line between Barapukuria and Bibiyana in Bangladesh. Power Systems Computer Aided Design (PSCAD) simulation tool is used to study both 400 kV single circuit and 400–230 kV double circuit transmission line. The objective of this study is to perform the single and three phase fault analysis in Bogura point and observe the situation of different bus during fault conditions. Result shows that for single circuit line the magnitude of three phase fault current is 16% higher than that of the single phase fault current. The double circuit line shows almost same magnitude of fault current for both of single and three phase fault in Bogura.","PeriodicalId":6721,"journal":{"name":"2020 IEEE Region 10 Symposium (TENSYMP)","volume":"32 1","pages":"1094-1097"},"PeriodicalIF":0.0000,"publicationDate":"2020-06-05","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Fault Analysis of High Voltage Transmission Line in Bangladesh: Barapukuria to Bibiyana\",\"authors\":\"A. Gupta, Hisham-Al-Rashid, Md. Zahidul Anam, Mohaimenul Islam\",\"doi\":\"10.1109/TENSYMP50017.2020.9230798\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"This paper reports a study on fault analysis on high voltage transmission line between Barapukuria and Bibiyana in Bangladesh. Power Systems Computer Aided Design (PSCAD) simulation tool is used to study both 400 kV single circuit and 400–230 kV double circuit transmission line. The objective of this study is to perform the single and three phase fault analysis in Bogura point and observe the situation of different bus during fault conditions. Result shows that for single circuit line the magnitude of three phase fault current is 16% higher than that of the single phase fault current. The double circuit line shows almost same magnitude of fault current for both of single and three phase fault in Bogura.\",\"PeriodicalId\":6721,\"journal\":{\"name\":\"2020 IEEE Region 10 Symposium (TENSYMP)\",\"volume\":\"32 1\",\"pages\":\"1094-1097\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2020-06-05\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"2020 IEEE Region 10 Symposium (TENSYMP)\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1109/TENSYMP50017.2020.9230798\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"2020 IEEE Region 10 Symposium (TENSYMP)","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1109/TENSYMP50017.2020.9230798","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

本文对孟加拉国巴拉普库里亚至比比亚纳高压输电线路的故障分析进行了研究。利用电力系统计算机辅助设计(PSCAD)仿真工具对400 kV单回和400 - 230 kV双回输电线路进行了仿真研究。本研究的目的是对Bogura点进行单相和三相故障分析,观察不同母线在故障状态下的情况。结果表明,对于单回路线路,三相故障电流的大小比单相故障电流的大小高16%。在博古拉,单相故障和三相故障的双回线显示出几乎相同的故障电流大小。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Fault Analysis of High Voltage Transmission Line in Bangladesh: Barapukuria to Bibiyana
This paper reports a study on fault analysis on high voltage transmission line between Barapukuria and Bibiyana in Bangladesh. Power Systems Computer Aided Design (PSCAD) simulation tool is used to study both 400 kV single circuit and 400–230 kV double circuit transmission line. The objective of this study is to perform the single and three phase fault analysis in Bogura point and observe the situation of different bus during fault conditions. Result shows that for single circuit line the magnitude of three phase fault current is 16% higher than that of the single phase fault current. The double circuit line shows almost same magnitude of fault current for both of single and three phase fault in Bogura.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信