{"title":"机房空调节能状态维护方法","authors":"J. Fajardo, Hermes Ramírez-León, D. Barreto, Carlos Rico, Camilo Cardona","doi":"10.1115/imece2022-91987","DOIUrl":null,"url":null,"abstract":"\n A Computer Room Air Conditioner (CRAC) system has been modeled and simulated to set up a Condition-based maintenance strategy oriented on the equipment’s energy efficiency performance (MCEE). The modeling was performed using ASPEN HYSYS based on actual performance conditions of a CRAC system in the Caribbean Colombia area. The condition-based was simulated based on a fouling model increase in the evaporator and condenser, decreasing the heat transfer process and increasing the heat loss. A 2-year fouling increase model was performed to obtain an economic-technical cost-function parameter and develop a cost-effective cleaning schedule for the evaporator and condenser. The results show a 5% COP decrease due to a fouling increase. The maintenance schedule for cleaning this system is cost-effective on the 310th day. Furthermore, a Critical Matrix of the CRAC performance is developed based on energy efficiency and a cost function.","PeriodicalId":23629,"journal":{"name":"Volume 6: Energy","volume":"29 1","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2022-10-30","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Energy Efficiency Condition-Based Maintenance Methodology for Computer Room Air Conditioners\",\"authors\":\"J. Fajardo, Hermes Ramírez-León, D. Barreto, Carlos Rico, Camilo Cardona\",\"doi\":\"10.1115/imece2022-91987\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"\\n A Computer Room Air Conditioner (CRAC) system has been modeled and simulated to set up a Condition-based maintenance strategy oriented on the equipment’s energy efficiency performance (MCEE). The modeling was performed using ASPEN HYSYS based on actual performance conditions of a CRAC system in the Caribbean Colombia area. The condition-based was simulated based on a fouling model increase in the evaporator and condenser, decreasing the heat transfer process and increasing the heat loss. A 2-year fouling increase model was performed to obtain an economic-technical cost-function parameter and develop a cost-effective cleaning schedule for the evaporator and condenser. The results show a 5% COP decrease due to a fouling increase. The maintenance schedule for cleaning this system is cost-effective on the 310th day. Furthermore, a Critical Matrix of the CRAC performance is developed based on energy efficiency and a cost function.\",\"PeriodicalId\":23629,\"journal\":{\"name\":\"Volume 6: Energy\",\"volume\":\"29 1\",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2022-10-30\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Volume 6: Energy\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.1115/imece2022-91987\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Volume 6: Energy","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.1115/imece2022-91987","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

本文对机房空调(CRAC)系统进行了建模和仿真,建立了以设备能效性能(MCEE)为导向的状态维护策略。根据加勒比海哥伦比亚地区CRAC系统的实际性能情况,使用ASPEN HYSYS进行建模。在蒸发器和冷凝器中增加污垢模型,降低了传热过程,增加了热损失。为了获得经济技术成本函数参数,并制定具有成本效益的蒸发器和冷凝器清洗计划,采用了2年的污垢增加模型。结果表明,由于污垢增加,COP降低了5%。清洗系统的维护计划在第310天是划算的。在此基础上,建立了基于能效和成本函数的CRAC性能临界矩阵。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Energy Efficiency Condition-Based Maintenance Methodology for Computer Room Air Conditioners
A Computer Room Air Conditioner (CRAC) system has been modeled and simulated to set up a Condition-based maintenance strategy oriented on the equipment’s energy efficiency performance (MCEE). The modeling was performed using ASPEN HYSYS based on actual performance conditions of a CRAC system in the Caribbean Colombia area. The condition-based was simulated based on a fouling model increase in the evaporator and condenser, decreasing the heat transfer process and increasing the heat loss. A 2-year fouling increase model was performed to obtain an economic-technical cost-function parameter and develop a cost-effective cleaning schedule for the evaporator and condenser. The results show a 5% COP decrease due to a fouling increase. The maintenance schedule for cleaning this system is cost-effective on the 310th day. Furthermore, a Critical Matrix of the CRAC performance is developed based on energy efficiency and a cost function.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
0
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信