冠状病毒大流行对大学办公楼电力质量的封锁影响及其替代解决方案

Ida Ayu Vadanti Locana Diwy, A. Rahardjo, Aji Nur Widyanto, F. Husnayain, R. Setiabudy
{"title":"冠状病毒大流行对大学办公楼电力质量的封锁影响及其替代解决方案","authors":"Ida Ayu Vadanti Locana Diwy, A. Rahardjo, Aji Nur Widyanto, F. Husnayain, R. Setiabudy","doi":"10.26418/elkha.v14i2.56226","DOIUrl":null,"url":null,"abstract":"The pandemic has changed the usage pattern of electrical appliances in buildings. This new pattern can create new problems in terms of power quality and thus affect the electrical system’s reliability. The purpose of this study is to determine the power quality of the Dean Office Building, Faculty of Engineering, Universitas Indonesia, and propose alternative solutions to its problems. To determine the quality of electric power, the related parameters such as voltage, current, power factor, and harmonics are measured first. The measurement results are compared with existing standards. If these standards cannot be met, damage to electrical equipment can occur. Out of eight parameters, three did not meet the criteria. First, overvoltage on average voltage with the range of 231.5-232.8 V. Second, IHDi nominal on the 3rd, 5th, 7th, and 15th harmonics for Thursday, April 7, 2022 on 06:11 with the value of 70.3%, 55.34%, 27.1%, and 8.07%. And third, the minimum power factor for the T phase with the value of 0.7219 is still less than 0.85. Possible solutions include checking and changing the supply transformer tap-changer, making an energy monitoring system and wiring diagram for understanding the load profile of the building, and using a single-tuned filter for harmonic currents.","PeriodicalId":32754,"journal":{"name":"Elkha Jurnal Teknik Elektro","volume":"44 10","pages":""},"PeriodicalIF":0.0000,"publicationDate":"2022-10-20","publicationTypes":"Journal Article","fieldsOfStudy":null,"isOpenAccess":false,"openAccessPdf":"","citationCount":"0","resultStr":"{\"title\":\"Lockdown Impact due to Corona Pandemic on Electric Power Quality and Its Alternative Solutions for a University Office Building\",\"authors\":\"Ida Ayu Vadanti Locana Diwy, A. Rahardjo, Aji Nur Widyanto, F. Husnayain, R. Setiabudy\",\"doi\":\"10.26418/elkha.v14i2.56226\",\"DOIUrl\":null,\"url\":null,\"abstract\":\"The pandemic has changed the usage pattern of electrical appliances in buildings. This new pattern can create new problems in terms of power quality and thus affect the electrical system’s reliability. The purpose of this study is to determine the power quality of the Dean Office Building, Faculty of Engineering, Universitas Indonesia, and propose alternative solutions to its problems. To determine the quality of electric power, the related parameters such as voltage, current, power factor, and harmonics are measured first. The measurement results are compared with existing standards. If these standards cannot be met, damage to electrical equipment can occur. Out of eight parameters, three did not meet the criteria. First, overvoltage on average voltage with the range of 231.5-232.8 V. Second, IHDi nominal on the 3rd, 5th, 7th, and 15th harmonics for Thursday, April 7, 2022 on 06:11 with the value of 70.3%, 55.34%, 27.1%, and 8.07%. And third, the minimum power factor for the T phase with the value of 0.7219 is still less than 0.85. Possible solutions include checking and changing the supply transformer tap-changer, making an energy monitoring system and wiring diagram for understanding the load profile of the building, and using a single-tuned filter for harmonic currents.\",\"PeriodicalId\":32754,\"journal\":{\"name\":\"Elkha Jurnal Teknik Elektro\",\"volume\":\"44 10\",\"pages\":\"\"},\"PeriodicalIF\":0.0000,\"publicationDate\":\"2022-10-20\",\"publicationTypes\":\"Journal Article\",\"fieldsOfStudy\":null,\"isOpenAccess\":false,\"openAccessPdf\":\"\",\"citationCount\":\"0\",\"resultStr\":null,\"platform\":\"Semanticscholar\",\"paperid\":null,\"PeriodicalName\":\"Elkha Jurnal Teknik Elektro\",\"FirstCategoryId\":\"1085\",\"ListUrlMain\":\"https://doi.org/10.26418/elkha.v14i2.56226\",\"RegionNum\":0,\"RegionCategory\":null,\"ArticlePicture\":[],\"TitleCN\":null,\"AbstractTextCN\":null,\"PMCID\":null,\"EPubDate\":\"\",\"PubModel\":\"\",\"JCR\":\"\",\"JCRName\":\"\",\"Score\":null,\"Total\":0}","platform":"Semanticscholar","paperid":null,"PeriodicalName":"Elkha Jurnal Teknik Elektro","FirstCategoryId":"1085","ListUrlMain":"https://doi.org/10.26418/elkha.v14i2.56226","RegionNum":0,"RegionCategory":null,"ArticlePicture":[],"TitleCN":null,"AbstractTextCN":null,"PMCID":null,"EPubDate":"","PubModel":"","JCR":"","JCRName":"","Score":null,"Total":0}
引用次数: 0

摘要

大流行改变了建筑物内电器的使用模式。这种新模式会产生电能质量方面的新问题,从而影响电力系统的可靠性。本研究的目的是确定印尼大学工程学院院长办公大楼的电力质量,并提出解决其问题的替代方案。为了确定电能的质量,首先要测量电压、电流、功率因数和谐波等相关参数。测量结果与现有标准进行了比较。如果不能满足这些标准,则可能发生电气设备损坏。在8个参数中,有3个不符合标准。一是过电压,平均电压的范围为231.5-232.8 V。其次,2022年4月7日星期四06:11 IHDi标称第3、5、7、15次谐波值分别为70.3%、55.34%、27.1%、8.07%。第三,T相的最小功率因数为0.7219,仍然小于0.85。可能的解决方案包括检查和更换电源变压器分接开关,制作能源监测系统和接线图以了解建筑物的负载概况,以及使用单调谐滤波器来处理谐波电流。
本文章由计算机程序翻译,如有差异,请以英文原文为准。
Lockdown Impact due to Corona Pandemic on Electric Power Quality and Its Alternative Solutions for a University Office Building
The pandemic has changed the usage pattern of electrical appliances in buildings. This new pattern can create new problems in terms of power quality and thus affect the electrical system’s reliability. The purpose of this study is to determine the power quality of the Dean Office Building, Faculty of Engineering, Universitas Indonesia, and propose alternative solutions to its problems. To determine the quality of electric power, the related parameters such as voltage, current, power factor, and harmonics are measured first. The measurement results are compared with existing standards. If these standards cannot be met, damage to electrical equipment can occur. Out of eight parameters, three did not meet the criteria. First, overvoltage on average voltage with the range of 231.5-232.8 V. Second, IHDi nominal on the 3rd, 5th, 7th, and 15th harmonics for Thursday, April 7, 2022 on 06:11 with the value of 70.3%, 55.34%, 27.1%, and 8.07%. And third, the minimum power factor for the T phase with the value of 0.7219 is still less than 0.85. Possible solutions include checking and changing the supply transformer tap-changer, making an energy monitoring system and wiring diagram for understanding the load profile of the building, and using a single-tuned filter for harmonic currents.
求助全文
通过发布文献求助,成功后即可免费获取论文全文。 去求助
来源期刊
自引率
0.00%
发文量
23
审稿时长
10 weeks
×
引用
GB/T 7714-2015
复制
MLA
复制
APA
复制
导出至
BibTeX EndNote RefMan NoteFirst NoteExpress
×
提示
您的信息不完整,为了账户安全,请先补充。
现在去补充
×
提示
您因"违规操作"
具体请查看互助需知
我知道了
×
提示
确定
请完成安全验证×
copy
已复制链接
快去分享给好友吧!
我知道了
右上角分享
点击右上角分享
0
联系我们:info@booksci.cn Book学术提供免费学术资源搜索服务,方便国内外学者检索中英文文献。致力于提供最便捷和优质的服务体验。 Copyright © 2023 布克学术 All rights reserved.
京ICP备2023020795号-1
ghs 京公网安备 11010802042870号
Book学术文献互助
Book学术文献互助群
群 号:481959085
Book学术官方微信